INSTALLATION
INSTALLATION AND CONNECTION OF FAN COMPONENTS (Version V)
Regulator connections
In order to install correctly, remove the power supply; undo the screw and lift off the cap. Fix the base to the wall through the special
holes, perform the electrical connections as per the diagram, put the cap back on the base and then close the device, by putting
the screw back on. For laying the cables, use some cable trays corresponding to CEI 23-32:
TECHNICAL CHARACTERISTICS
POWER SUPPLY:
230V~ +10/-15% 50Hz
PROTECTION:
Internal fuse 500mA T RIT
THERMOSTAT:
Intervention allowed at 50°C
DIMENSIONS:
145x67x30 mm
CONTAINER:
V0 IP40 ABS
PTC PROBE
External non polarised probe
REGULATOR CONNECTIONS
1
Power supply
Neutral
Colour:
Blue
2
Power supply
Phase
Colour:
Brown
3
Power supply
Earth
Colour:
Green/Yellow
4
Motor cable
Earth
Colour:
Green/Yellow
5
Motor cable
Neutral
Colour:
Blue
6
Motor cable
Phase
Colour:
Brown
7-8
External probe
non pol. Colour:
Grey
FUSE: the device is protected against short circuits or overloads by an internal fuse to the container of the regulator. If the fuse
fails, proceed as follows:
1. Remove the power supply to the regulator and eliminate the cause leading to the failure of the fuse
2. Open the container as described previously
3. Replace the faulty fuse with a new, approved delayed 500mA fuse
4. Close the container again and provide power to the device again
PTC PROBE
230V AC 50Hz
IRREVERSIBLE CONNECTOR
AIR B
O
X MOTOR EBM D2E120
®