Seebacher GmbH
www.seebacher.de
Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz
Fax: +49 (0) 80 41 / 77 77 2
5
9. Product description
With the I/O module I/O-08B-230V-10A 8 circuits with a maximum of
230V/10A (2 contacts each on a common root) can be switched. As
inputs 8 optocoupler inputs 12-48V on a common reference poten-
tial are available. All inputs and outputs are freely programmable in
the functions via the software.
Inputs / Outputs
• 8 relay outputs 230V/10A, 2 contacts each on a common root can be loaded with 10A
• 8 optocoupler inputs 12-48V
Function displays
• 1 red LED indicates the operating voltage
• 1 flashing yellow LED indicates the communication with the master via subnet
• 8 green LEDs signalize the current output states
Connections
• 1 connection for the subnet (BUS A and B, RS-485)
• 1 connection for the operating voltage (Ub, 0V)
• 8 outputs (2 each on a common connection)
• 8 inputs (on a common reference terminal)
• 2 P-COM connections (subnet and operating voltage)
Design
• DIN rail mounted plastic housing light grey, snap-on on 35mm DIN rail 6 HP
Special function DIP switch 1 = Emergency operation
• Switch „OFF“ = BUS operation
• Switch „ON“ = Emergency operation
(8x impulse switching function: input E1 switches output A1, input E2 switches output A2, etc.)
NEW!! The following functions can be parameterized
• Status of the output relays after Power ON
• Definition of the inputs as currentless OFF or ON
• Definition of the functions of the BUS inputs
• Definition of the functions in the operating modes: BUS, BUS failure and emergency operating
• Safety functions for motor controls (limit switch setup, interlockings, definable unlock times, switch-on times)
• Specification of defined pulse times on the relays
• Definition of the display LEDs at the module (indication inputs or outputs, BUS error, operating mode, chaser)