Foundation Requirements

 

Wood floor framing systems are suitable foundations 

for the Vent-Free fireplace. Because the Vent-Free fireplace is 

listed for “zero clearance” at the unit bottom, sides, back and 

top it may sit directly upon wood sub-flooring.

 

The  Vent-Free  fireplace  weighs  approximately  750-

900 lbs. (excluding gas log appliance and finish trim). Since 

this weight is spread over an area of seven and one-half square

feet (7.5 sq. feet) to nine and one half square feet (9.5 sq. feet)

depending on standard unit size chosen, it is necessary that any 

wood floor framing where this unit is placed be designed to 

carry concentrated loading of approximately 150 lbs/sq. foot. 

 

Standard  residential  concrete  slab  is  a  suitable 

foundation. This may be either a structural off-grade slab or a 

structural slab-on-grade.

Wood Sub-Floor

Wood Floor

Joist System

Standard Residential

Concrete Slab

On or Off-Grade

Содержание VF-36

Страница 1: ...cit installation and operation instructions INSTALLER Leave this manual with the appliance CONSUMER Retain this manual for future reference Be Sure to Read Entire Manual Before Beginning Construction Contents of this manual may change without prior notification FOR USE ONLY WITH DECORATIVE TYPE CERTIFIED VENT FREE GAS LOG DO NOT BUILD A WOOD FIRE Carefully review the instructions supplied with the...

Страница 2: ...n 11 Specialty Application 12 See Thru 12 Noncombustible Finished Facing Requirements Clearance to Combustible Trim 13 Summary 14 Notes 15 Warranty Note Illustrations shown in this manual are not to scale and are intended to show typical installations Nominal dimensions are given for design and framing reference only since actual installations may vary due to job specific design preferences Howeve...

Страница 3: ...on However all such trim material must meet standard fireplace code requirements non combustible facing material must be applied to a minimum of eight inches 8 beyond the sides of the finished opening of the Vent Free fireplace and non combustible facing material must cover a minimum of twelve inches 12 above the finished opening of the installed unit Reference Intertek Testing Services Report No ...

Страница 4: ...1 2 3 20 5 A C 25 B Model A B C 36 43 36 1 8 27 1 4 42 49 43 1 8 46 53 47 1 8 33 1 4 37 1 4 37 1 2 43 W x 37 1 2 H x 25 1 4 D 49 W x 37 1 2 H x 25 1 4 D 53 W x 37 1 2 H x 25 1 4 D MINIMUM FRAMING 715 lbs 820 lbs 880 lbs WEIGHT B See Thru Models Side View Front View Plan View 3 31 1 37 1 ...

Страница 5: ... Size 36 42 46 Quantity 3 3 3 BASE TOP PLATE Model A 36 43 42 49 46 53 SIDE WALL BACK WALLS Model A 36 43 42 49 46 53 A 10 1 2 2 5 10 1 2 2 5 3 5 Earthcore reserves the right to make changes at any time without notice in design materials and specifications Earthcore further reserves the right to discontinue styles and products Please call 1 800 642 2920 for an Isokern dealer near you ...

Страница 6: ...trim Since this weight is spread over an area of seven and one half square feet 7 5 sq feet to nine and one half square feet 9 5 sq feet depending on standard unit size chosen it is necessary that any wood floor framing where this unit is placed be designed to carry concentrated loading of approximately 150 lbs sq foot Standard residential concrete slab is a suitable foundation This may be either ...

Страница 7: ...es B Framed Opening A Framed Opening C The following chart of dimensions is intended to aid in the positioning of a Vent Free fireplace in a corner condition Firebox A B C D Model 36 43 49 3 4 32 1 2 49 Model 42 49 52 3 4 37 71 3 4 Model 46 53 54 3 4 39 1 2 74 1 2 Notes A A reflects the Vent Free Series base plate dimension B B reflects the Vent Free Series outside center of firebox base plate to ...

Страница 8: ... mating components are assembled Face and Surface Cracks Should a face crack appear after the unit is assembled the crack can be repaired in place A crack can be V notched with a masonry chisel to a depth of approximately three eighth inch 3 8 Earthcore Mortar is then squeezed into the face crack and troweled smooth to the surface of the component Note Badly fragmented components should be discard...

Страница 9: ... plus the one and one half inch 1 1 2 thick fire brick floor in addition to the height of the concrete block platform For a flush hearth fireplace floor flush with the room s floor the base plate can be omitted from the assembly and the firebox walls built directly on the concrete support slab as long as there are no wood underpinnings This makes the fireplace finished fire brick floor approximate...

Страница 10: ...rbon monoxide detector be installed Gas line for gas log sets used in the Vent Free firebox can be routed through the side wall back wall or floor of the firebox by drilling an appropriately sized hole using a masonry drill bit Electrical Line Feed can be routed through the firebox back wall side walls or floor by drilling an appropriately sized hole using a masonry drill bit Be sure to follow the...

Страница 11: ...d It takes a total of about five gallons of mortar mix dry measure to fire brick line a Vent Free Face joints of one quarter inch 1 4 to three eighths inch 3 8 give a good appearance to the finished brick work however larger face joint dimensions are also acceptable Step 1 Wet mop the inside of the Vent Free with a damp sponge to remove dust and loose particles from the interior before installing ...

Страница 12: ...or two sided Vent Free fireplaces can be constructed from the standard one sided unit components by eliminating the back wall assembly In this installation the standard side wall components are reversed so that the standard side wall taper sits to the outside of the box leaving the inside of the see thru firebox with two straight and parallel interior walls Angle steel three inch by three inch by ...

Страница 13: ...asure of twenty four inches 24 away from the finished opening of the Vent Free fireplace Mantle and Mantle Shelf Clearance Vent Free fireplace are subject to the same building code safety clearances from the firebox opening as with any fireplace opening Parts of the combustible mantle assembly located above and projecting more than one and one half inches 1 1 2 inches from the firebox opening shal...

Страница 14: ...anufacturer s agent or supplier Dual Listed Appliance The Vent Free fireplace is certified with the use of dual listed unvented gas log heaters with a maximum input of 40 000 Btu s Do not burn any other type of vented gas log fire wood paper or refuse in the Vent Free fireplace Fuel Do not introduce any type of fuel into the Vent Free fireplace other than the LP or Natural Gas listed for use in th...

Страница 15: ...15 Notes ...

Страница 16: ...ision thereof is not responsible for any labor costs or indirect costs incurred for the replacement of defective components Earthcore is not responsible for misuse or mishandling of components Nothing in this warranty makes Earthcore or any division thereof liable in any respect for any injury or damage to the building or structure in which the fireplace or chimney system has been installed or to ...

Отзывы: