iSMA-B-AAC20/Sedona Modbus
Version 1.3
www.gc5.pl
Page 28 / 55
Device disabled - Device is disabled,
Network disabled
–
Modbus Network is disabled.
Fault Cause
–
Fault cause description,
Fault Status
–
Point error status (true
–
point read/write error),
Enable
–
Point enable/disable („true”
-
Point enable, „false”
- Point disable),
Address Format
–
Register address format, available options: Modbus, Decimal,
Address
–
Register address,
Poll Frequency
–
Reading poll frequency, available options: Fast, Normal, Slow,
Write Type
–
Writing mode, available options: COV
–
only on input change,
COV_PollFrequency
–
on input change and periodically, PollFrequency - only periodically,
Trigger
–
Remote force sending trigger (on rising edge),
Out
–
Output slot, current value of read/write registry,
In
–
Input slot.
5.4.3
Modbus TCP Numeric Point
ModbusClientNumericPoint is a component which is responsible for reading numeric values
from the device. The component has Read action available under the right mouse button,
which forces the reading of the point.