![iSMA 4I4O-H Скачать руководство пользователя страница 69](http://html.mh-extra.com/html/isma/4i4o-h/4i4o-h_user-manual_2093180069.webp)
iSMA-B-MINI/MIX Modbus User Manual
www.ismacontrolli.com
DMP262en | 1st Issue rev. 8 | 05/2022
page 69 of 107
Modbus
Address
Decimal
Address
Hex
Address
Register Name
Access
Description
40150
149
0x95
DEFAULT STATE OF
ANALOG OUTPUT 6
Read/write
Memory
40151
150
0x96
UNIVERSAL INPUT
CONFIGURATION 1
Read/write
Memory
Configuration of universal
input and type of
temperature sensor
The default value is 1
Valu
e
Description /
Sensor
0
Resistance
measurement
off
1
10K3A1 NTC
2
10K4A1 NTC
3
10K NTC Carel
4
20K6A1 NTC
5
2,2K3A1 NTC
B=3975K
6
3K3A1 NTC
7
30K6A1 NTC
8
SIE1
9
TAC1
10
SAT1
16
Pt1000
17
Ni1000
+128
Voltage
measurement
off
40152
151
0x97
UNIVERSAL INPUT
CONFIGURATION 2
Read/write
Memory
40153
152
0x98
UNIVERSAL INPUT
CONFIGURATION 3
Read/write
Memory
40154
153
0x99
UNIVERSAL INPUT
CONFIGURATION 4
Read/write
Memory
40155
154
0x9A
UNIVERSAL INPUT
CONFIGURATION 5
Read/write
Memory
40156
155
0x9B
UNIVERSAL INPUT
CONFIGURATION 6
Read/write
Memory
40157
156
0x9C
UNIVERSAL INPUT
CONFIGURATION 7
Read/write
Memory
40158
157
0x9D
UNIVERSAL INPUT
CONFIGURATION 8
Read/write
Memory
40159
158
0x9E
FILTER TIME
CONSTANT
OF THE UNIVERSAL
INPUT 1
Read/write
Memory
Filter time constant,
expressed in seconds in the
range from 0 to 60 seconds
A value of 0 disables the
filter
The default value is 2 s