SfAR-S-8TO User Manual
www.ismacontrolli.com
DMP277en | 3rd Issue rev. 2 | 05/2022
page 17 of 20
Modbus
Address
Decimal
Address
Hex
Address
Register Name
Access
Description
20026
25
0x19
Default Duty Cycle
Output 7
Read/write
Value default duty
cycle output 7
From 0 to 100%
20027
26
0x1A
Default Duty Cycle
Output 8
Read/write
Value default duty
cycle output 8
From 0 to 100%
40033
32
0x20
Received Packets LSR
(Least Significant
Register)
Read/write
No. of received
packets
40034
33
0x21
Received Packets MSR
(Most Significant
Register)
Read/write
40035
34
0x22
Incorrect Packets LSR
Read/write
No. of received
packets with error
40036
35
0x23
Incorrect Packets MSR
Read/write
40037
36
0x24
Sent Packets LSR
Read/write
No. of sent packets
40038
37
0x25
Sent Packets MSR
Read/write
40052
51
0x33
Outputs
Read/write
Outputs state
40133
132
0x84
Period PWM Output 1
Read/write
Range adjustment
period:
0-65535 [s]
40134
133
0x85
Period PWM Output 2
Read/write
Range adjustment
period:
0-65535 [s]
40135
134
0x86
Period PWM Output 3
Read/write
Range adjustment
period:
0-65535 [s]
40136
135
0x87
Period PWM Output 4
Read/write
Range adjustment
period:
0-65535 [s]
40137
136
0x88
Period PWM Output 5
Read/write
Range adjustment
period:
0-65535 [s]
40138
137
0x89
Period PWM Output 6
Read/write
Range adjustment
period:
0-65535 [s]
40139
138
0x8A
Period PWM Output 7
Read/write
Range adjustment
period:
0-65535 [s]