SfAR-S-6TI User Manual
www.ismacontrolli.com
DMP272en | 3rd Issue rev. 2 | 05/2022
page 22 of 26
Modbus
Address
Decimal
Address
Hex
Address
Register Name
Access
Description
40079
78
0x4E
Alarm Settings 5
Read/write
40080
79
0x4F
Alarm Settings 6
Read/write
40081
80
0x50
Constant Junction
Temperature
Read/write
Value of junction
temperature
40082
81
0x51
Junction Temperature
Offset
Read/write
Junction temperature
offset
40083
82
0x52
Input 1 Settings
Read/write
Analog input mode:
0 – input disabled
1 – voltage to 2048 mV
2 – voltage to 256 mV
3 – J thermocouple
4 – K thermocouple
5 – T thermocouple
6 – N thermocouple
7 – S thermocouple
8 – R thermocouple
9 – B thermocouple
10 – Pt100 3-wire
11 – Pt100 2-wire
12 – resistance to 8 kΩ
13 - Ni100
14 – KTY81-110
15 – Pt500 3-wire
16 – Pt500 2-wire
17 – Pt1000 3-wire
18 – Pt1000 2-wire
+32 – junction
temperature is taken from
register 40081 "Constant
junction temperature"
40084
83
0x53
Input 2 Settings
Read/write
40085
84
0x54
Input 3 Settings
Read/write
40086
85
0x55
Input 4 Settings
Read/write
40087
86
0x56
Input 5 Settings
Read/write
40088
87
0x57
Input 6 Settings
Read/write
40089
88
0x58
Output 1 Settings
Read/write
Alarm output settings
0 – output is set by PLC
+1 – temperature from
input 1
+2 – temperature from
input 2
+4 – temperature from
input 3
+8 – temperature from
input 4
+16 – temperature from
input 5
+32 – temperature from
input 6
+256 – Output is set if
value is greater than
Alarm Value (register
40091 or 40092)
(„cooling")