turn the DIP switch SW6 on;
turn the power on;
when power and communication LED is lit, turn the switch SW6 off.
4.7 Configuration Registers
Modbus Address
Decimal Address
Hex Address
Name
Values
40003
2
0x02
Baud Rate
0 – 2400
1 – 4800
2 – 9600
3 – 19200
4 – 38400
5 – 57600
6 – 115200
other – value * 10
40005
4
0x04
Parity
0 – none
1 – odd
2 – even
3 – always 0
4 – always
40004
3
0x03
Stop Bits
1 – one stop bit
2 – two stop bits
40004
3
0x03
Data Bits
7 – 7 data bits
8 – 8 data bits
40006
5
0x05
Response Delay
Time in ms
40007
6
0x06
Modbus Mode
0 – RTU
1 – ASCII
Table 6. Configuration registers
Warning!
After restoring the default configuration, all values stored in the registers will be
cleared as well.