background image

www.ismacontrolli.com

The performances stated in this sheet can be modifi ed without any prior notice.

page 1

DIM262en | 1

st

 Issue rev. 3 | 07/2022

MVH56Ex

Valve Actuators with Emergency Fail-safe Function

INSTALLATION

Hot media hazard. Before removing actuator from valve or 

opening the valve, ensure that the valve control medium is iso-

lated and remove the pressure. Work should only be carried 

out by a competent engineer.

 

Note: 

do not use the actuator disassembled from 

the valve.

MVH56EA

For valve with 16 and 25mm stroke

•  Rise the valve stem;

•  Lock the stem extension c on the rack completely re-

tracted placing the indicator disk a, the jagged washer b 

and the nut f positioned half of the extension itself.

For valves with 45mm stroke

•  Rise the valve stem;

•  Lock the stem extension c on the rack completely re-

tracted placing the indicator disk a and the jagged washer 

b.

Assemble the actuator to the valve by U-bolt 

(d)

 and the two 

nuts 

(e)

 without locking the nuts.

•  Raise the valve stem.

•  Remove the cover and rotate the pivot clockwise so that 

the rack comes out for assembling it with the valve stem; 

the pivot can be locked by a spanner as shown in the pi-

cture.

•  Rotate the actuator to screw the extension on the valve 

stem, so lock it tightening the nut on the stem.

•  Tighten the two nuts on the U-bolt to lock the actuator.

•  Remove the key from the pivot and mount the small cap. 

1

1a

2

3

Содержание MVH56Ex

Страница 1: ... re tracted placing the indicator disk a the jagged washer b and the nut f positioned half of the extension itself For valves with 45mm stroke Rise the valve stem Lock the stem extension c on the rack completely re tracted placing the indicator disk a and the jagged washer b Assemble the actuator to the valve by U bolt d and the two nuts e without locking the nuts Raise the valve stem Remove the c...

Страница 2: ...ension c on the rack completely extended placing the indicator disk a and the jag ged washer b Remove the cover Rotate the pivot 1 2 turn counter clockwise and lock it by a spanner as shown in the picture Screw the extension on the valve stem until the groove on the actuator base coincides with the one on the valve then lock the extension tightening the nut on the stem In case the two bases do sti...

Страница 3: ... Label Description Function Min Wire Size AWG Max Wire Length L1 24 V AC DC Power Supply 1 5mm2 AWG16 75 m Ln 0 V Y 0 10 V DC Modulating Control Input 0 5mm2 AWG20 200 m M 0 V Common Y1 Open Floating Control Input 0 5mm2 AWG20 200 m Y2 Close V 16Vdc Voltage Output max 25mA 0 5mm2 AWG20 200 m M 0 V Common U 2 10 V DC Feedback Output Signal 0 5mm2 AWG20 200 m M 0 V Common Terminals correspondence wi...

Страница 4: ... Controller MVH56Ex 24Vac 24Vdc 0V Modulating control 0 10Vcc L1 Ln Y M N B Signals M and Ln are internally connected MVH56Ex contain a half wave rectifier power supply They must not be powered with transformers that are used to power other devices using not isolated full wave rectifier power supply DIP SWITCHES SETTINGS Set the DIP switches according to the tables here below In order to be sure t...

Страница 5: ...ting Control 0 10Vdc DIP n 2 OFF only Modulating Control 2 10Vdc DIP n 2 OFF only 5 Sequence Control 0 5Vdc with DIP n 4 OFF only Sequence Control 2 6Vdc with DIP n 4 ON only DIP n 3 ON only Sequence Control 5 10Vdc with DIP n 4 OFF only Sequence Control 6 10Vdc with DIP n 4 ON only DIP n 3 ON only 6 Voltage Input Signal input between Y and M Current Input Signal 4 20mA input between Y and M In th...

Страница 6: ...dition and then after 10s the actuator updates the new stroke length During these 10s RED LED is ON The actuator tries 5 times against the new stall condition At the end of the attempts the fault will be signalled RED LED ON The actuator does not update the new stroke length but after 60s makes other attempts to verify the stall condition Valve stuck Inverted control signal 4 RED Quick Blin king G...