DIP Switch

OFF

ON

1

MVH56EA

Direct Action

Reverse Action

MVH56EC

Reverse Action

Direct Action

2

MVH56EA

Modulating Control (MOD) (Input between Y [+] and 

M [-])

3 point floating (INC) ( Y1 open , Y2 close connected 

L1 or Ln if powered in Vacd; if powered in Vdc con-

nected necessarily to Ln )

MVH56EC

Modulating Control (MOD) (Input between Y [+] and 

M [-])

3 point floating (INC) ( Y1 open , Y2 close connected 

L1 or Ln if powered in Vacd; if powered in Vdc con-

nected necessarily to Ln )

3

-

Selection of sequence mode, control range defined 

by SW 5

4

Modulating Control 0-10Vdc 

(DIP n. 2 OFF only)

Modulating Control 2-10Vdc 

(DIP n. 2 OFF only)

5

Sequence Control 0-5Vdc  with DIP n. 4 OFF only 

Sequence Control 2-6Vdc  with DIP n. 4 ON only 

(DIP n. 3 ON only)

Sequence Control 5-10Vdc  with DIP n. 4 OFF only 

Sequence Control 6-10Vdc  with DIP n. 4 ON only 

(DIP n. 3 ON only)

6

Voltage Input Signal 

(input between Y [+] and M [-])

Current Input Signal 4-20mA (input between Y [+] and 

M [-]). 

In this case DIP n. 4 must be set to ON.

7

Automatic Calibration: the actuator updates the 

stroke range every time an unexpected mechanical 

stop is detected for at least 10s

Manual Calibration: the actutor calibration is started 

moving the DIP from OFF to ON; if the DIP is left in ON 

the actuator will never update the calibrated stroke 

value even when an unexpected endpoint is detected

Содержание MVH56Ex

Страница 1: ... re tracted placing the indicator disk a the jagged washer b and the nut f positioned half of the extension itself For valves with 45mm stroke Rise the valve stem Lock the stem extension c on the rack completely re tracted placing the indicator disk a and the jagged washer b Assemble the actuator to the valve by U bolt d and the two nuts e without locking the nuts Raise the valve stem Remove the c...

Страница 2: ...ension c on the rack completely extended placing the indicator disk a and the jag ged washer b Remove the cover Rotate the pivot 1 2 turn counter clockwise and lock it by a spanner as shown in the picture Screw the extension on the valve stem until the groove on the actuator base coincides with the one on the valve then lock the extension tightening the nut on the stem In case the two bases do sti...

Страница 3: ... Label Description Function Min Wire Size AWG Max Wire Length L1 24 V AC DC Power Supply 1 5mm2 AWG16 75 m Ln 0 V Y 0 10 V DC Modulating Control Input 0 5mm2 AWG20 200 m M 0 V Common Y1 Open Floating Control Input 0 5mm2 AWG20 200 m Y2 Close V 16Vdc Voltage Output max 25mA 0 5mm2 AWG20 200 m M 0 V Common U 2 10 V DC Feedback Output Signal 0 5mm2 AWG20 200 m M 0 V Common Terminals correspondence wi...

Страница 4: ... Controller MVH56Ex 24Vac 24Vdc 0V Modulating control 0 10Vcc L1 Ln Y M N B Signals M and Ln are internally connected MVH56Ex contain a half wave rectifier power supply They must not be powered with transformers that are used to power other devices using not isolated full wave rectifier power supply DIP SWITCHES SETTINGS Set the DIP switches according to the tables here below In order to be sure t...

Страница 5: ...ting Control 0 10Vdc DIP n 2 OFF only Modulating Control 2 10Vdc DIP n 2 OFF only 5 Sequence Control 0 5Vdc with DIP n 4 OFF only Sequence Control 2 6Vdc with DIP n 4 ON only DIP n 3 ON only Sequence Control 5 10Vdc with DIP n 4 OFF only Sequence Control 6 10Vdc with DIP n 4 ON only DIP n 3 ON only 6 Voltage Input Signal input between Y and M Current Input Signal 4 20mA input between Y and M In th...

Страница 6: ...dition and then after 10s the actuator updates the new stroke length During these 10s RED LED is ON The actuator tries 5 times against the new stall condition At the end of the attempts the fault will be signalled RED LED ON The actuator does not update the new stroke length but after 60s makes other attempts to verify the stall condition Valve stuck Inverted control signal 4 RED Quick Blin king G...

Отзывы: