DIP Switch
OFF
ON
1
MVH56EA
Direct Action
Reverse Action
MVH56EC
Reverse Action
Direct Action
2
MVH56EA
Modulating Control (MOD) (Input between Y [+] and
M [-])
3 point floating (INC) ( Y1 open , Y2 close connected
L1 or Ln if powered in Vacd; if powered in Vdc con-
nected necessarily to Ln )
MVH56EC
Modulating Control (MOD) (Input between Y [+] and
M [-])
3 point floating (INC) ( Y1 open , Y2 close connected
L1 or Ln if powered in Vacd; if powered in Vdc con-
nected necessarily to Ln )
3
-
Selection of sequence mode, control range defined
by SW 5
4
Modulating Control 0-10Vdc
(DIP n. 2 OFF only)
Modulating Control 2-10Vdc
(DIP n. 2 OFF only)
5
Sequence Control 0-5Vdc with DIP n. 4 OFF only
Sequence Control 2-6Vdc with DIP n. 4 ON only
(DIP n. 3 ON only)
Sequence Control 5-10Vdc with DIP n. 4 OFF only
Sequence Control 6-10Vdc with DIP n. 4 ON only
(DIP n. 3 ON only)
6
Voltage Input Signal
(input between Y [+] and M [-])
Current Input Signal 4-20mA (input between Y [+] and
M [-]).
In this case DIP n. 4 must be set to ON.
7
Automatic Calibration: the actuator updates the
stroke range every time an unexpected mechanical
stop is detected for at least 10s
Manual Calibration: the actutor calibration is started
moving the DIP from OFF to ON; if the DIP is left in ON
the actuator will never update the calibrated stroke
value even when an unexpected endpoint is detected