MVC503R-MB Configuration Tool
–
Product Manual
15
•
Low Voltage/Failsafe:
it shows the low supply voltage anomaly events as well as
the number of emergency return events.
•
High Voltage:
it shows the high supply voltage anomaly events.
•
Unexpected Stall:
it shows the unexpected stall events, that is how many times
a stall has occurred inside the range stroke.
•
Extra Stroke:
it shows an extra stroke anomaly compared to the calculated
stroke during the calibration phase (stroke out of range).
•
FW Version:
it shows the actuator firmware version.
Reset Actuator:
SW reset of the actuator is executed by pressing the “
RESET
”
button. Before to send others commands to the actuator it is necessary to wait
the supercap recharge phase is completed. In case of changes in the actuator
configuration parameters, press the “RESET” button to make the changes
immediately effective.
The parameters in the “Actuator Status” box are read at the connection start
-up and
every time the label near the textbox is clicked.
The information relating to the “Events” section can be read all 6 simultaneously
by pressing the text “
Counters
”.
3.7
“A
ctuator Command
”
Box
In this box it is possible to set the actuator position in the range of 0-100% and verify
the position (feedback).
Figure
16. Actuator command box
•
Command signal:
it allows to set the modbus command for the actuator
positioning in the range 0-100%.
Press
“
Write Device
”
or
the “ENTER” key to send the position command to
the actuator.
•
Feedback:
allows to verify the current position of the actuator in the range 0-
100%. A value of 110% indicates that the actuator is in emergency return phase,