Installing the Electrical Conduit:  

Knockout holes for connecting the electrical conduits are located at the top left and right of the Wall Box. 

 

Connect rigid conduit for the required 120-vac electrical service. 

 

Connect conduit for the operating power to the upper left top of the enclosure at the junction box. 

 

Connect conduit for the operating power for the output to the upper right top of the enclosure.

 

 
Wiring the Unit: 
Important! 

Verify that the electrical supply is disconnected prior to connecting wiring to the DLA Controller. 
 

To wire the Controller: 
1.

 

Remove the junction box cover. 

2.

 

Make final connections to the 120-vac electrical service to wiring within the junction box.  Verify that line wiring 
(Black), neutral (White), and ground wire (Green) are correctly connected.               

       Minimum recommended wire size is 14 AWG. 
3.

 

Replace the junction box cover before activating or testing the unit. 

 

Optional Input Control circuit:

 

24-vac/vdc active OFF inputs can be connected at CON 4-B and 4-C (JP 11 determines 4-C usage).  Refer to jumper 
configuration chart   Make connection from only one source at each connector terminal. 
 

Remote Panic Input Connection: 

 

Flow Sensors and/or moisture sensors providing dry-contact outputs are connected to the PCB at CON 4-a.  Flow Sensors 
should have the time delay function set to the approximate time needed by ice maker machines to cycle so that this process 
will not inadvertently trip the Unit to OFF.  An optional Remote Panic Button can also be connected at the CON 4-A 
 

Optional Panic Output Terminal: 

A configurable Panic output is activated at CON 5.  See configuration chart and location of this connector on page 5. 

 

Connection of the Wall Panel Plug:

 

The Unit is equipped with a 9 pin d-sub connector 

 

Turn counter-clockwise the two retaining clips at the top of the Panel, and open. 

 

 Insert plug onto circuit header on PCB. 

 

Turn Power 

ON

.   

 

Close the panel and lock. 

CAUTION!  

Do not install the panel until all wall finishes are complete. Verify that the plug is configured correctly.  

Incorrect insertion will prevent operation of unit.

 

 
Important! 
All local codes must be followed when installing this unit and when connecting the conduit to the service panel and 
making wiring connections.  Do not install wiring or cable for integrated systems, remote panic assemblies or other 
interface wiring within conduit for either 24-vac control or 120-vac line voltage.  Each wiring system including 
outputs should be housed in independent conduit and not bundled with wiring for other systems. Failure to comply 
with these wiring specifics may create transient voltage at the pc board and cause system malfunction and/or failure.

 

 
Operation of the Unit: 

Engage the OPERATE Switch.  The circuit will activate and the panel Green LED above that switch will illuminate to 
indicate that the Unit is actively monitoring the water flow within the residence.  To turn OFF the Monitoring function of the 
unit, engage or the OPERATE Switch to the OFF position.  Once the Unit is in the OFF mode, it will be necessary to re-
engage the SERVICE ON switch in order to reactivate the service.   
 
The Green LED above the SERVICE ON Switch will illuminate if the water service solenoid is open. 
 
Once in the Panic Mode the SERVICE Switch must be engaged in order to reactivate service.  All Input Signals must be 
withdrawn prior to reactivation.  If it is desired to have the water service valve ON without re-activating the monitoring 
function of the unit, then engage only the SERVICE Switch.

 

 
 

Содержание RLA-1

Страница 1: ...eak Detection Installation Operations Start up and Maintenance Instructions Table of Contents Page Warranty 2 Enclosure Specifications and Dimensions 3 Styles 3 Model Number 3 Mounting Instructions Fl...

Страница 2: ...operation Periodic testing should be conducted by the user to assure that all components function and operate according to specifications Care should be taken in the installation of this product ISIME...

Страница 3: ...owder coated sheet metal 8 0 X 14 25 X 4 0 all dimensions are in inches Style Output Circuits Trans former Switch Breaker pcb Fuse 1 Output Rating standard Pulse Output RLA 1 1 24 vac 2 amp 5 amp 2 am...

Страница 4: ...it is necessary to attach the provided brackets to the rear of the housing Care should be taken to verify that the mounting means securely fastens the unit to the wall surface A stainless skirt is pr...

Страница 5: ...C The 24 vac dc Inputs will accept a single signal from a sole monitoring or control device to turn OFF the water supply Output Circuit Terminal The solenoids provided are ISIMET S 220 Series General...

Страница 6: ...page 5 Connection of the Wall Panel Plug The Unit is equipped with a 9 pin d sub connector Turn counter clockwise the two retaining clips at the top of the Panel and open Insert plug onto circuit hea...

Страница 7: ...rst review the installation and wiring portions of this manual prior to placing the unit in service ISIMET recommends that piping systems be thoroughly flushed and cleaned and tested for leaks prior t...

Страница 8: ...8 ISIMET MAPA LLC PO Box 129 Mailing 103 W CJ Wise Pkwy Naples Texas 75568 0129 Phone 866 897 0737 Fax 903 897 0740 www ISIMET com Innovative Systems Integrating Mechanical and Electrical Technology...

Отзывы: