4.4 Analog Output Wiring
L- 102DA
1
Connect To
J1
J2
4 – 20mA Output
Main Board
J2 Connector
0 – 10V Output
4
Analog Output Board
12
Страница 1: ...ISI 799 Service Manual 0 ...
Страница 2: ...1 3 2 Main Menu 6 1 3 3 Configuration Menu 7 1 3 4 Calibration Menu 8 1 3 5 Serial Communication Menu 9 1 3 6 Print Format Menu 10 1 3 7 Analog Output Menu 10 1 3 8 Digital Input Output Menu 11 1 3 9 Test Menu 12 1 3 10 Version 12 2 0 Serial Communication Format 8 3 0 Error Messages 9 4 0 Appendix 9 4 1 Load Cell Wiring 9 4 2 RS 232 Wiring 10 4 3 Digital Output and Input Wiring 11 4 4 Analog Outpu...
Страница 3: ... PW0099 when press ENTER key Method 2 Open back cover of indicator then press K1 located bottom right side of PCB board 1 2 Exit Configuration and Calibration When span calibration is done indicator is returned to weigh mode automatically On the other way the is pressed at CONFIG menu 1 3 Menu Structures and Parameter Descriptions 1 3 1 Key Functions In Setup Mode ON OFF ZERO TARE UNITS SET PRINT ...
Страница 4: ...G 1d 10 none 3d 0 0000 20 0 00000 50 ZRANGE AUZERO MOTBAN FILT CKWCOD PCS 2 ZERO 1d 0 0 YES 100 NOZERO 3d 1 1 NO 5d 10d 7 4 Parameter Descriptions 1 DECPNT Decimal Point Decimal point location in the primary unit display 2 CAP Capacity Weigh capacity up to 999999 can be entered 3 DSPDIV Display Division Selects the minimum increment weigh value for primary unit The value is from 1 to 50 4 P NUIT P...
Страница 5: ...ABLE lights 10 FILT Digital filter The bigger number the stronger filter 11 CKWCOD Check weight condition 0 Check on Counting mode and unstable 1 Check on Counting mode and stable 2 Check on Weighing mode and unstable 3 Check on Weighing mode and stable 4 Disable check function 12 PCS Counting mode Enable Counting mode or not 1 3 4 Calibration menu CONFIG CALIB SERIAL PFORMT ALGOUT DIG IO TEST VER...
Страница 6: ...r Descriptions 1 BAUD Baud rate The transmission speed for serial RS 232 port 2 BITS Bits The number of data bits and parity of data are transmitted 3 TERMIN Termination Termination character 4 FUNCTN Functions of Transmission Select CONTIN the RS 232 port is for data continue transmission Select DEMAND the RS 232 port is for data transmission when the PRINT key is pressed or the is received 5 ...
Страница 7: ...include consecutive number If select 3 the print format include ID number and consecutive number 2 ID ID number Edit and Enter ID number 3 W FMT Weigh format If select GTN the gross tare and net weigh are printed in print format If select NET The net weigh is printed in print format 1 3 7 Analogue output menu CONFIG CALIB SERIAL PFORMT ALGOUT DIG IO TEST VERS SOURCE MIN MAX TWZERO TWSPAN GROSS num...
Страница 8: ...weak span Adjust the analog output span calibration Use a multimeter to monitor analog output value 10VDC for 0 10VDC 20mADC for 4 20mADC Edit the number press ENTER to save new value 1 3 8 Digital Input Output Menu CONFIG CALIB SERIAL PFORMT ALGOUT DIG IO TEST VERS DIG IN DIGOUT ZERO 0 TARE 1 UNITS PRINT Parameter Descriptions 1 DIG IN Digital Input Selects the keypad functions for digital input ...
Страница 9: ...00 2 0 Serial Communication Format STX PL WWWWWWW UNIT G N S TERM ASC I I 02 decimal Polarity Space Positive Negative Weight 7 digits with decimal point Leading zero transmitted as space G Gross CR LF N Net or CR Status space valid L pounds M Motion K kilograms H Over G grams A Accept O ounces L Under space none U Under Over Load Continuous Output Data Format 8 ...
Страница 10: ...s Un Under load OL Over load Error 1 Span calibration error Error 2 Analog out span calibration error 4 0 Appendix 4 1 Load Cell Wiring J1 Loadcell 1 EXC 2 EXC 3 SHILD 4 SIG 5 SIG K1 K2 K3 K4 K5 K6 K7 Load Cell Wiring 9 ...
Страница 11: ...4 2 RS 232 Wiring J1 Loadcell RS 232 RX TX GND K2 K3 K4 K5 K6 K7 RS 232 Wiring 10 ...
Страница 12: ...J1 Loadcell 1 2 J2 15 16 K2 K3 K4 K5 K6 K7 Digital Output and Input J2 Connector J2 Pin Label Function 10 GND GND 11 DIN Digital Input 13 DO1 Digital Output 1 14 DO2 Digital Output 2 15 DO3 Digital Output 3 16 5 5VDC J2 Connector Assignment 11 ...
Страница 13: ...4 4 Analog Output Wiring L 102DA 1 1 Connect To J1 J2 4 20mA Output Main Board J2 Connector 0 10V Output 4 Analog Output Board 12 ...
Страница 14: ...SETTINGS FOR ISI 99 INDICATOR DEC POINT 0 0 CAPACITY 200 0 DSPDIV 1 P UNIT LB LB KG YES ZRTBN 1d ZRANGE 100 AUZERO ZERO MOTBAN Id FILT 2 CKWCOD 4 PCS NO SERIAL COMMUNICATION SETTINGS UNDER SERIAL BAUD 9600 BITS 8 NONE TERMIN CR LF FUNCTN CONTIN ...