Function 

Operation 

Parameter

 

Menu 

Location 

Factory 
Default 

Operating 

Range 

Unit 

Auxiliary 

Differential 

Heater or Dry Contact 

Hysteresis 

*1

 

Shy 

Hidden 

Menu 2 

1 - 45 

°F 

Maximum 

Temperature 

Alarm 

Alerts with “HA” when 

maximum temperature has 

been exceeded 

ALU 

Hidden 

Menu 2 

105 

45 - 302 

°F 

Minimum 

Temperature 

Alarm 

Alerts with “LA” when 

minimum temperature has 

been exceeded 

ALL 

Hidden 

Menu 2 

45 

-67 - 105 

°F 

 

*1

Note:

 When both Heater and Dry Contact options are included, these parameters only control Heater 

Settings.  Dry Contact is controlled by ALU.

 

 
 

      Alarms Signals 

Message 

Cause 

Outputs

 

“P1” 

Enclosure Probe Failure 

Start and stop of the compressor after 15 minute 

intervals 

*2

 

“P2” 

Condenser Probe Failure 

No Output

 *2

 

“HA” 

Maximum Temperature Alarm: P1 > 105°F for 3 

minutes (after initial 30 min. start up delay) 

No Output

 *2

 

“LA” 

Minimum Temperature Alarm: P1 < 45°F for 3 

minutes (after initial 30 min. start up delay) 

No Output

 *2

 

“HA2” 

Condenser High Temperature Alarm: P2 > 145°F for 

3 minutes 

Compressor Off

 *2

 

“LA2” 

Condenser Low Temperature Alarm: P2 < 50°F for 3 

minutes 

No Output

 *2

 

“CA” 

Evaporator Coil Alarm: Low Pressure for 2 minutes 

Compressor Off

 *2

 

“noP” 

Invalid Probe Selected: Low Evaporator Coil 

No Output, Display Only 

 

*2

Note:

 When both Heater and Dry Contact options are included, Dry Contact (Alarm Contact) Relay is 

activated.

 

 

 

ALARM RECOVERY

…….. 

 

If the compressor is turned off due to an alarm, it will be able to restart after the 

AC

 anti short-cycle time delay. 

(Parameter AC = 5minutes) 

 

 

Probe 

alarm

 P1

 is cleared with no time delay after the fault is cleared. 

 

Probe 

alarm 

P2

 starts and stops with no time delay. 

 

Temperature 

alarm 

HA 

automatically clears as soon as the temperature returns to below 105

°F (the 

ALU

 setpoint) -2°F = 103°F. 

 

Temperature 

alarm 

LA 

automatically clears as soon as the temperature returns to above 55

°F (the 

ALL

 setpoint) +2°F = 47°F. 

 

Temperature 

alarm 

HA2 

automatically clears as soon as the condenser coils temperature returns to below 135

°F. 

 

Temperature 

alarm 

LA2 

automatically clears as soon as the condenser coils temperature returns to above 60

°F. 

 

Temperature 

alarm 

CA 

automatically clears as soon as the pressure returns to normal.

 

 
 
 
 

Содержание HC201 Series

Страница 1: ...User Technical Manual HC201 Series Rev 1 0...

Страница 2: ...roprietary information comprising ISC Inc s trade secrets Please maintain the confidentiality of all proprietary information during and after the term of the use agreement Also please refrain from usi...

Страница 3: ...onditioner 4 Moving the Air Conditioner 5 Unit Label 5 Operation 6 Preliminary Testing 6 Mounting the Air Conditioner 7 Unit Specifications 8 Options 10 System Faults 13 Digital Temperature Controller...

Страница 4: ...nt ISC air conditioning equipment is designed manufactured and packed to prevent damage from normal handling shock and vibration during shipment It is necessary to inspect your equipment upon receipt...

Страница 5: ...ry compressors without damaging the compressor If air conditioner is to be shipped or transported at any time pack in original packaging and strap to pallet to prevent damage Air conditioner must be k...

Страница 6: ...In the event of excess water vapor where the enclosure door has been left open there is an overflow hole on the bottom of every unit Please contact ISC Inc if you encounter excess water coming from y...

Страница 7: ...where the cold air can circulate across the width of the enclosure to cool it all the way across Once proper mounting placement is determined turn the enclosure equipment off if possible to prevent d...

Страница 8: ...ltage Range Volts Inrush Current Start Up Current Amps Loading Current Running Current Amps SCCR Short Circuit Current Rating Amps Recommended Circuit Protection Amps KVA Rating K Watts Refrigerant Ty...

Страница 9: ...4421 Tradition Trail Plano Texas 75093 972 964 2700 800 836 7472 URL www iscenclosurecooling com Email iscinfo iscsales com SP ENG 211 100 11 Rev 1 0 9 P a g e THIS PAGE IS INTENTIONALLY LEFT BLANK...

Страница 10: ...um constant low current in the compressor motor during the non cooling state This option provides internal heat to the compressor to protect it from stalls and hard starts during long periods of compr...

Страница 11: ...0 Watt 150 Watt 200 Watt 250 Watt 300 Watt 400 Watt 550 Watt 650 Watt 950 Watt Default Settings 55 F Heat Set Point 3 F Differential At the default settings the heater output turns on at 52 F and oper...

Страница 12: ...t any specific location of your enclosure Ethernet IP Controller Output This option provides the ability to communicate with the ISC Air Conditioner controller via the Ethernet IP protocol You can mon...

Страница 13: ...delay A thermal overload protects the compressor against faults In the event that the snowflake status LED is not flashing on the display and the compressor is not running an internal fault may have...

Страница 14: ...display its value 4 Use the UP or DOWN arrow key to change its value 5 Press SET to store the new value and move to the following parameter To exit Press SET UP arrow keys or wait 15 seconds without...

Страница 15: ...start up delay No Output 2 HA2 Condenser High Temperature Alarm P2 145 F for 3 minutes Compressor Off 2 LA2 Condenser Low Temperature Alarm P2 50 F for 3 minutes No Output 2 CA Evaporator Coil Alarm L...

Страница 16: ...ray bottle is recommended to enhance air filter efficiency Replacement filters are readily available from ISC Customer Service DO NOT operate the air conditioner without the air filter Such operation...

Страница 17: ...HC201 32008 1 Compressor HC201 31040 1 Compressor Thermal Overload Internal Gasket Installation Kit 71405 HC20 Evaporator Fan 41062 2 1 Condenser Fan 41060 2 1 Filter Media 44013 1 Capacitor HC201 54...

Страница 18: ...n position ON OFF Toggle Switch then Retry Verify input power meets voltage requirements as shown in the UL label YES If problem is still present contact technical support Unit Overheats Insufficient...

Страница 19: ...se meter 3 Check for faulty evaporator fan 3 Measure Temperature at Evaporator Verify Heat Load Requirements Is unit capacity adequate for internal head load Possible low refrigerant Is compressor the...

Страница 20: ...ontroller CA YES NO Check Low Pressure Switch Connections and Verify Pressure switch is closed Use meter 3 P1 or P2 NO YES Check probe connections potential faulty probe LA LA2 HA HA2 YES Refer to Ala...

Страница 21: ...Dimensions 230 VAC Models Water overflow excessive Check drain is it plugged YES NO Clean condensate pan and drain add 1 tbsp bleach to upper pan monthly to kill mold Is Air Conditioner sealed agains...

Страница 22: ...4421 Tradition Trail Plano Texas 75093 972 964 2700 800 836 7472 URL www iscenclosurecooling com Email iscinfo iscsales com SP ENG 211 100 11 Rev 1 0 22 P a g e 480 VAC Models...

Страница 23: ...s com SP ENG 211 100 11 Rev 1 0 23 P a g e Electrical Schematics System Schematic Digital Controller Schematic Note Schematics applies to all voltages optional accessories wiring not provided in this...

Страница 24: ...lacement of its own product This Warranty does not cover Labor or reimbursement of labor for evaluation removal installation repair or cost of any warranted part except at the ISC factory in Dallas Te...

Страница 25: ...nd contact info email phone number and address Shipping method Pack unit in a suitable packing for shipment preferably the original packaging if available If suitable packing is not available arrange...

Отзывы: