Use and maintenance manual

13.

FAULTS - TECHNICAL AFTER-SALES ASSISTANCE

USER

CAUSE

SOLUTION

THE EQUIPMENT 

DOES NOT WORK

Blown protective fuse

First find the cause of the trip 

of the switch, and then replace the new fuse.

The master switch is open

Close the master switch.

The plug is not inserted

Insert the plug.

Electrical black-out

If the black-out should be prolonged, transfer the product into 

an appropriate cold storage container.

THE TEMPERATURE 

IS NOT SUFFICIENTLY 

LOW

Evaporator(s) completely blocked 

with ice

Carry out an additional defrosting cycle.

Wrong temperature setting

Set the appropriate temperature.

Equipment being struck by 

currents of air or exposed to 

direct or reflected sunlight

Remove any draughts and prevent any direct or reflected 

sunlight.

Insufficient air flow for 

cooling to the condenser

Remove anything which could obstruct 

the circulation of air through the condenser (sheets of paper, 

cardboard, insufficient slots in grille, etc.).

THE COMPRESSOR

DOES NOT START 

WORKING OR WORKS FOR

VERY SHORT PERIODS

No electric power supply 

to the appliance

Check if there is a power cut.

Close the various switches on the power supply line.

Excessively low power voltage

Check that the mains voltage of the power 

supply cable corresponds to the nominal value 220V +/- 10%.

Temperature set too high

If the temperature is higher than the air temperature 

in the display chamber, the compressor will not start.

Set the suited temperature if the current temperature 

is not low enough.

If the appliance is not working properly or stops working, before contacting the 

Customer Support Centre

 check the following:

TECHNICAL ASSISTANCE

CAUSE

SOLUTION

THE TEMPERATURE 

IS NOT SUFFICIENTLY 

LOW

Internal ventilators 

not working 

or damaged fans

Replace the ventilators/fans.

Thermostat / 

Electronic control board 

not efficient

Replace the thermostat/electronic control board.

If the electronic control board is used on appliances with R290 

coolant, it must only be replaced with an original spare part 

supplied by the manufacturer. Replace the temperature probes 

only after having ascertained which of them 

is inefficient.

Condensing unit blocked 

with dust or dirt 

in general

Clean the condensing unit thoroughly. 

The condensing unit in particular operating environments 

(e.g. presence of dust, presence of excessive humidity, etc.) 

when the performance of the appliance deteriorates requires 

careful cleaning.

Insufficient refrigerant 

load in the 

cooling system

Find the cause of the refrigerant loss and remove it; 

top up the refrigerant load if necessary having emptied 

the system.

THE COMPRESSOR

DOES NOT START WORK-

ING OR WORKS FOR

VERY SHORT PERIODS

Maximum pressure 

switch triggered 

(if present)

Check the reasons why the pressure switch is operating at 

maximum pressure levels, such as: air condenser obstructed, 

condenser fan with air stopped, ambient 

temperature too high, pressure switch defective.

Содержание GE MY20

Страница 1: ...Via Madonna di Campagna 123 06083 Bastia Umbra PG Italy T 39 075 801 71 F 39 075 800 09 00 E customerservice isaitaly com www isaitaly com 1 GE MY20 IT 2020 02 428001235037 Use and maintenance manual...

Страница 2: ...S 14 9 1 RISK OF CONTACT WITH LIVE PARTS 14 9 2 FIRE 14 9 3 EXPLOSIVE ATMOSPHERE 14 9 4 SLIPPING 14 9 5 TRIPPING 14 10 DISPOSAL OF WASTE MATERIAL 15 11 INSTALLATION 16 11 1 UNPACKING 16 11 2 HANDLING...

Страница 3: ...MANUAL DANGER ENERGISED ELECTRICAL PARTS ATTENTION DANGER INFORMATION VISUAL OBSERVATION DANGER SLIPPING DANGER TRIPPING EARTHING USE OF PROTECTIVE CLOTHING REQUEST FOR MAINTENANCE OR OPERATIONS THAT...

Страница 4: ...ger than 8 and by persons with reduced physical sensory or mental capabilities or lacking experience or necessary knowledge as long as supervised or after having received training regarding safe use o...

Страница 5: ...cessories that modify the use of the same and use of spare parts different to those recommended can become the cause of injury DANGER Any work conducted on the appliance must involve disconnection fro...

Страница 6: ...orrect use in particular the tech nical description of the various functional units accessories and safety systems op eration use of instrumentation and interpretation of any diagnostic warnings main...

Страница 7: ...y To ensure operator safety appliance devices should be kept in constant working order This manual is intended to illustrate the use and maintenance of the appliance The operator has a responsibility...

Страница 8: ...alified personnel that has been to work with flammable refrigerants R290 The refrigerant R290 is a gas that is compatible with the environment but is extremely flammable Be very careful when transport...

Страница 9: ...sources of ignition away from the appliance Properly ventilate the premises for a few minutes Turn the unit off pull the plug Notify the customer service department The more refrigerant containing an...

Страница 10: ...luded in the warranty Incorrect use of the appliance Incorrect connection to the power grid Normal wear of the components such as breakage of the compressors of the neon LED lights etc if not due to m...

Страница 11: ...e for the product 2 Conformity marking 3 Type 4 Model name 5 Article 6 Manufacturing Date 7 Production order 8 Customer order 9 Product class 10 Serial number 11 Owner registration number 12 Power sup...

Страница 12: ...n of TB ICE CREAM CHILLED FROZEN PRODUCTS TN PATISSERIE PRE PACK FRESH PRODUCTS The manufacturer is not liable for injury to persons or damage to property or the appliance itself caused by the display...

Страница 13: ...y 8 5 WARNING SIGNS IF ANY The equipment is equipped with danger attention and obligation warning plates defined in accordance with the legislation on graphic symbols to be used on the systems The pla...

Страница 14: ...levant limiting devices It is strictly forbidden to conduct any electrical modification in order to prevent additional unforeseen hazards and risks 9 2 FIRE DANGER In the event of a fire immediately d...

Страница 15: ...ials according to their similar features Check the type of refrigerant on the plate inside the counter remove the refrigerant and dispose of it through the authorised services Disconnect the evaporato...

Страница 16: ...ials are recyclable and should be disposed of in accordance with local regulations All packaging materials are recyclable and should be disposed of in accordance with the local regulations Please dest...

Страница 17: ...17 GE MY20 IT 2020 02 428001235037 Use and maintenance manual 11 1 UNPACKING 2 3...

Страница 18: ...to install near a heat source use a suitable insulating plate Also avoid exposure to direct solar irradiation all of this causes the temperature inside the refrigerated compartment to rise with negat...

Страница 19: ...NG ATTENTION It is fundamental to respect the distances indicated mm for correct installation of the appliance 11 7 LEVELLING ATTENTION The equipment is fitted with height adjustable levelling feet af...

Страница 20: ...NING CHECK COMPRESSOR OIL LEVEL whenever present AIR TANK DRAINING whenever present CONTROL PNEUMATIC CONNECTIONS whenever present CHECK THE INTEGRITY OF THE COOLING SYSTEM PIPES INSPECT THE CABLES AN...

Страница 21: ...is higher than the air temperature in the display chamber the compressor will not start Set the suited temperature if the current temperature is not low enough If the appliance is not working properl...

Страница 22: ...22 GE MY20 IT 2020 02 428001235037 Use and maintenance manual 14 TECHNICAL SPECIFICATIONS Model External dimensions mm Weight kg Length Depth Height Net 700 710 871 2090 125 871 710...

Страница 23: ...TION It is absolutely essential to observe the max loads indicated 40 MAX 40 MAX 40 MAX Adjustable display shelves 14 2 CLOSURE WITH KEY ATTENTION The appliance is equipped with a lock with key for cl...

Страница 24: ...making sure that the same has an earth contact and that there are no multiple sockets connected The appliance will start working automatically NO SWITCH OFF OFF Remove the power plug manually 15 CONTR...

Страница 25: ...erformed STAND BY ESC Press and release Goes back up one level with respect to current menu Confirms parameter value Activates the Stand by function INSTRUMENT ON OFF Press for more than 5 seconds to...

Страница 26: ...utput not active Setting in C dro 0 Other ALARMS FAULT CAUSE E1 Probe 1 Reading of values outside the operating range Probe faulty Short circuited Open E2 Probe 2 Defrost Reading of values outside the...

Страница 27: ...the appliance It is advisable in this regard to wait until the following day to make sure that the defrost has been fully performed Do not use mechanical devices or other means to accelerate the defr...

Страница 28: ...ours until every piece of equipment on the condenser unit has reached a temperate close to room temperature Access the Condenser Unit as indicated below Clean the condenser using a dedicated soft bris...