Doc. SIE10169 Rev. 13 Page 12 of 32
. Type of current source: electronic constant current generator, driven by a discharging capacitor.
. Current generation duration: minimum 30 ms, according to the test current and the load.
. Capacitor charging time: 60 s.
. Maximum test voltage: 18 V.
. Test mode selection. With single test, the resistance value is displayed. With Circuit Breaker test,
the screen shows a table that collects the measurement of all phases.
. NOTE: during the first 4 ms, the resistance measurement is affected by the connection leads
inductance.
2.9
D
YNAMIC RESISTANCE MEASUREMENT
(OPTIONAL)
With this measurement it is possible to record the main contact resistance during the CB close.
The CB is open prior to test start: CBA2000 issues the Close command; as the contact closes, the
test current passes through the contact, and CBA1000 measures the contact resistance variations
during the close movement.
. Test current, resistance ranges and other characteristics: as for the static resistance measurement.
. Unlike the static resistance measurement, the test result is not a table of resistance measurements:
it is the resistance profile during the test, along with voltage and current profiles.
2.10
T
EST SET CONTROL
. The control is local, via keypad, selectors and display: no PC control is necessary.
. Keypad: 12 keys, numeric plus alphabet: it allows inputting all test references. The arrangement is
the same as portable phones.
. Two dedicated pushbuttons for test start and sequence selection.
. Numeric encoder with pushbutton for menu selection (see below the selections list).
. Five pushbuttons as menu shortcuts
. As the test is started, a buzzer warns the operator.
. The graphical display has the following main features:
-
Type: transflective LCD;
-
Pixels: 320x 240;
-
Backlight color: white;
-
View area: 122 x 92 mm;
-
Displays: menu selections prior to test start; then, current waveforms, contact inputs (main –
resistance), auxiliary inputs, analog input (those enabled). For dynamic resistance, it is
possible to display the resistance profile, along with voltage and current profiles.
. Memory size: 256 Mbytes (approx. 500 results).
. Maximum record length: 200 s.
. Capability of saving and re-calling up to 64 test settings.
2.11
D
ATA MANAGEMENT
The communication to the PC can be performed via two communication ports:
. RS232; baud rate 57600;
. USB.
Test results can be saved into an USB pen memory: this allows transferring all test results to the
office without the need of transporting the test set.