Chassis Ground Connection
The IES12G chassis ground connection, located next to the terminal block, uses a #6-32 Screw. We
recommend terminating the ground connection using a #6 ring lug, and a torque setting of 15 in.lbs
(1.7Nm).
2.4
Rear Panel
The components on the rear of the IES12G are shown below:
1.
Screw holes (4) for wall mount kit.
2.
DIN-Rail mount
Figure 3
–
Rear Panel
100-240VAC rated equipment: A 250VAC appropriately rated circuit
breaker must be installed.
Equipment must be installed according to the applicable country wiring
codes.
When equipped with a HI voltage power supply and DC backup,
independent sources can be used to power the product for greater
redundancy.
120-370VDC rated equipment: A 370VDC appropriately rated circuit
breaker must be installed.
A circuit breaker is not required for DC power supply voltages of 10-48VDC.
For Dual DC power supplies, separate circuit breakers must be installed and
separately identified.
Equipment must be installed according to the applicable country wiring
codes.