IRT DDA-4280 Скачать руководство пользователя страница 13

4280-dda.ib.rev0.doc 

Page 13 of 17

 

11/03/2009

 

Operation

 

 

Stand-alone operation: 

When used in a stand-alone situation, that is non-hand shaking mode, the DDA-4280 behaves as a standard 
2.048 Mb/s G.703 distribution amplifier. 
 
One input is electronically split into four outputs. On loss of power to the unit the input is automatically bypassed to 
output 1 via on board relays. 
 
A loss of power alarm and general alarm (loss of signal, AIS detect) is provided by relay contacts to open circuit via 
the Krone connector on the rear assembly, see 

Installation

 section of this manual for connections. 

 
Front panel LEDs indicate the presence of a valid input signal (In Service (Main) – green), the absence of a valid 
input signal (Data Loss – Red) and the detection of an alarm indication signal within the inputted signal (AIS – Red). 
The Standby LED (green) is not used in the stand-alone operation. 
 
The front panel 

change

 switches do not work when used in a stand-alone operation. 

 

Handshake operation: 

When used  in the handshake mode, two cards fit side by side plugged into a ZDA-4300RH. The ZDA-4300RH 
provides the necessary interconnect controls to automatically switch between the input signals to the outputs, 
provided that the toggle switch on the front panels of the units are set to Change Allow and not Change Inhibit. 
Automatic switching parameters are set by a loss of input condition and switch SW3 settings as described in the 

Configuration

 section of this manual. 

 
When the toggle switch is set to 

Change-Inhibit

 both automatic and manual switching of the input signals is not 

possible. 
 
When the units are first turned on one unit will take the responsibility of being 

In Service (Main)

 whilst the other will 

become the 

Standby

 unit. It may be necessary to manually swap the two states if they do not start in the required 

configuration by pressing the front panel manual switch on the unit that is desired to be acting as the 

In Service

 

module. Note that in order to do so the toggle switch should also be set to the 

Change-Allow

 position on both 

modules. 
 
Loss of power alarms and general (loss of signal, AIS detect) alarms are provided by relay contacts to open circuit 
via two Krone connectors on the rear assembly. External changeover request is also provided via these same Krone 
connectors. 

In Service (Main)

 tally indication is via a third Krone connector, see 

Installation

 section of this manual 

for connections. 
 
Front panel LEDs, on both units, indicate the presence of a valid input signal (In Service (Main)  – green, or 
Standby - green ), the absence of a valid input signal (Data Loss  – Red) and the detection of an alarm indication 
signal within the inputted signal (AIS – Red). 
 
 
 

Содержание DDA-4280

Страница 1: ...manufactured in Australia IRT can be found on the Internet at http www irtelectronics com I R T Electronics Pty Ltd A B N 35 000 832 575 26 Hotham Parade ARTARMON N S W 2064 AUSTRALIA National Phone...

Страница 2: ...at Is It 14 DDA 4280 SNMP Functions 16 Maintenance Storage 17 Warranty Service 17 Equipment return 17 This instruction book applies to units later than S N 0901001 Operational Safety WARNING Operation...

Страница 3: ...by Changeover inhibit and changeover request switches are provided on the front panel for use where modules are linked in pairs for redundancy For this configuration the double width rear assembly is...

Страница 4: ...Y RL1 2 RELAY RL5 2 RL2 1 RL2 1 RL3 RL3 Output Driver FPGA E1Generator Change over logic AIS Detector INPUT SK5 RL1 2 OUTPUTS SK4 Data Reg with Jitter Att MON SK2 Block diagram DDA 4280 Signal path SK...

Страница 5: ...has failed General alarm Contact to open circuit if Data Loss is detected OR AIS is detected Connectors Data BNC Alarm Krone LSA plus Indicators Data loss AIS detect Module in service Module in standb...

Страница 6: ...using the failed path DDA to become Standby This implies that when the failed path is restored that it will remain as Standby and not become Main unless either a failure of Main occurs or a manual cha...

Страница 7: ...signal at various points in the DDA when in operation They are not intended as accurate portrayals of either voltage levels or timing It can be seen that the original signal has both positive and nega...

Страница 8: ...F Disable switching on AIS input when used in handshaking mode ON Enable switching on AIS input when used in handshaking mode SW4 5 Not used SW4 6 Not used SW4 7 Not used SW4 8 Not used NOTE AIS stand...

Страница 9: ...e is connected to earth for safety reasons See frame manual for details Signal earth For safety reasons a connection is made between signal earth and chassis earth No attempt should be made to break t...

Страница 10: ...s reflection problems with G 703 signals causing data errors In general cable runs should be kept as short as possible and should not exceed 200 metres for reliable error free operation Handshake alar...

Страница 11: ...up with the three sets of multipin sockets on the main PCB module Align all pins and then gently press the SMU 4000 all the way down into place If the SMU 4000 is not already programmed with the corr...

Страница 12: ...order and approximate layout only 1 2 3 4 OUTPUT 4 INPUT PL4 SK 13 SK 4 SK 9 SK 8 SK 6 OUTPUT 2 OUTPUT 3 OUTPUT 1 PL5 SK 5 N140 MON ALLOW INHIBIT REQUEST AIS STANDBY CHANGE DATA LOSS MAIN DDA 4280 ZDA...

Страница 13: ...front panels of the units are set to Change Allow and not Change Inhibit Automatic switching parameters are set by a loss of input condition and switch SW3 settings as described in the Configuration s...

Страница 14: ...that information into a form compatible with SNMP The agent therefore acts as an interface between the NMS and the managed devices The NMS sends a request message and control commands for the managed...

Страница 15: ...MP compatible need a plug in SMU 4000 module with a program relevant to the module that it is plugged into Depending on the module besides the module identification parameters such as alarm states inp...

Страница 16: ...4280 dda ib rev0 doc Page 16 of 17 11 03 2009 DDA 4280 SNMP Functions At the time of writing this manual SNMP functions were still to be written for the DDA 4280 Contact IRT for update of status...

Страница 17: ...extended by IRT only to the extent obtainable from the component supplier Equipment return Before arranging service ensure that the fault is in the unit to be serviced and not in associated equipment...

Отзывы: