Manufactured Home Installations

(ref. 

Figure 7

)

This appliance is approved for installation into a manufactured 

(mobile) home in the USA ONLY!

Installation should be in accordance with the Mobile Home 

Construction and Safety Standard, Title 24 CFR, Part 3280 (in 

Canada CAN/CSA Z240 MH), or, when such a standard is not 

applicable, the Standard for Mobile Home Installations, ANSI 

A225.1.

All mobile home installations require an outside air kit (see 

Page 27

 

for ordering information). The stove must be secured to the floor and 

grounded to the chassis of the mobile home.

WARNING:  DO NOT INSTALL IN SLEEPING ROOM OF A MOBILE 

HOME.

CAUTION:  THE STRUCTURAL INTEGRITY OF THE MOBILE HOME 

FLOOR, WALL AND CEILING/ROOF MUST BE MAINTAINED.

Approved Chimney - 

Your stove is approved for use with Class A, UL 

103 HT (U.S.) / ULC-S629 (Canada) Listed Residential Type and Building 

Heating Appliance Chimney (HT chimney - 2100° Fahrenheit) and double 

wall connector pipe

.  

Approved chimney brands are Security Chimneys™,

 

Jakes Evans/GSW, Dura-vent, Metal Fab, Ameri-Tec, Metalbestos and 

Industrial Chimney (ICC).

Clearances to connector shall be measured from 6” flue collar. Restric-

tions apply! Read instructions before installing.

YOUR CHIMNEY INSTALLATION MUST COMPLY WITH LOCAL 

BUILDING AND FIRE CODES.

Termination Cap 

with Spark Arrestor

Remove, if mobile 

home is transported

Storm 

Collar

Flashing

Support

Box

DVL Close 

Clearance 

Connector Pipe

Floor

Protector

3 Feet

Minimum

7 Feet 

Minimum

Double Wall Pipe

Using 6” or 8” Diameter Type L-Vent Connector Pipe

Mobile (Manufactured) Home Installation Shown

Figure 7 - Typical Installation

Minimum of 

12-15’ of Flue 

to achieve a 

stable draft.

Fasten each stove pipe 

connection with at least 

3 sheet metal screws.

Mobile home installations 

require a spark arrestor at the 

chimney termination.

All mobile home installa-

tions require an outside 

air kit (see 

Page 27

 for 

ordering information) 

and the stove must be 

secured to the floor and 

grounded to the mobile 

home chassis.

Install Outside Air 

Kits per instructions 

on 

Page 11

INSTALL VENTING SYSTEM PER VENT MANUFACTURERS 
INSTRUCTIONS!

Fasten stove pipe to 

flue collar using 3 

sheet metal screws.

Secure Stove

to floor

Grounded to Steel Chassis 

using a #8 AGW copper 

wire or equivalent.

Chassis

Floor

CHIMNEY INSTALLATION

•  Install chimney as per manufacturer’s instructions. Some brands of 

pipe may require removal of the spacer ring in the flue collar.

•  All horizontal runs of pipe should be as short as possible and are 

required by NFPA No. 211 to have an upward pitch or rise in the same 

direction the smoke travels of no less than 1/4” to the linear foot. The 

connector pipe must meet minimum clearances in any direction to 

walls or other combustible materials. It must attach to a listed double 

wall metal chimney at least 6” in diameter or to a masonry chimney 

with a flue passage of at least 48 square inches.

•  It is required that a chimney connector pipe not extend further than 

the inner wall of the flue when it is connected to a masonry chimney 

and that it either be cemented to the masonry or be installed without 

cement in a thimble connected to the masonry wall. When the 

connector is inserted into a thimble, the joint must be tight enough 

so that it will not be dislodged in normal use. Install connector at 

no less than the minimum clearances from the ceiling when using a 

90-degree elbow to pass through combustible constructions.

•  Chimney connector pipes should never pass through a floor, ceiling, 

fire wall, partition, or combustible construction of any type unless 

certain precautions are taken. The best method is to use a listed 

thimble and a listed chimney in accordance with the manufacturer’s 

directions. NFPA No. 211 gives approved methods for passing a flue 

pipe through combustible constructions (see 

Page 10

).

Stove

Side View

Содержание Canyon ST310

Страница 1: ...ch manual is available upon request Order P N 900134 00 Ce manuel d installation est disponible en francais simplement en faire la demande Num ro de la pi ce 900134 00 This appliance must be properly...

Страница 2: ...roper Venting System 4 Negative Pressure Warning 5 Creosote 5 Disposal of Ashes 5 Fuel 5 Paint Curing 5 Burn In Period 5 Clearances to Combustibles 6 7 Floor Protection 6 7 Alcove Clearances 6 Chimney...

Страница 3: ...during the burn ing season to check for soot and creosote accumulations Any accumulations over 1 8 thick should be removed by a professionalchimneysweep Donotattempttoburnoutheavy creosoteaccumulation...

Страница 4: ...he connected appliance in accordance with the manufacturer s instructions Chimney Guidelines This appliance requires approximately 12 feet minimum of effective draw provided by the venting system As a...

Страница 5: ...reate dangerous back drafting of the stove and chimney joints drawing combustion by products into the home Be sure your home has adequate makeup air to eliminate negative pressures caused by the above...

Страница 6: ...nd the total vent length above the flue outlet exceeds 14 feet it is recommended that the 8 to 6 pipe reducer is used and a 6 venting system be installed This appliance may be vented into a code appro...

Страница 7: ...l distances should be measured from the stove s flue collar 2 Minimum noncombustible hearth pad dimensions 3 Not applicable to alcove installations 4 In corner applications when installed at minimum b...

Страница 8: ...r Figure 5 Typical Installation Figure 6 Connected to a Masonry Chimney Floor Protector Floor Protector Fasten each stove pipe connection with at least 3 sheet metal screws Single wall stove pipe must...

Страница 9: ...ermination All mobile home installa tions require an outside air kit see Page 27 for ordering information and the stove must be secured to the floor and grounded to the mobile home chassis Install Out...

Страница 10: ...ll be 12 in 305 mm Chimney section concentric with and spaced 1 in 25 4 mm away from connector by means of sheet steel support plates on both ends of chimney section Opening shall be covered and chimn...

Страница 11: ...nd remove the contents upon receipt and check for any damaged or missing parts If there is hidden damage notify your freight company or IHP dealer immediately CAUTION Wear gloves during installation i...

Страница 12: ...asher and screw in that leg as well 9 Install bricks and baffle as per instructions on Pages 14 and 15 It is highly recommended that the baffle be assembled before the chimney is installed so that the...

Страница 13: ...le s center should be 3 76 mm directly forward from the center of the flue outlet or locate as per the instructions below 6 Position the stove on your floor protection in the exact location where it i...

Страница 14: ...nit Once you have the first two boards installed slide the board to the left side of the baffle support all the way to the left and rear of the unit You will slide the board to the right side of the s...

Страница 15: ...X 8 3 4 B 6 1 2 X 4 1 2 C 3 1 2 X 9 D 1 1 2 X 4 1 2 E 3 7 8 X 9 F 4 1 2 X 9 H 3 1 2 X 4 1 2 K 3 X 7 M 4 1 2 X 4 1 2 Figure 14 26 B 27 B 28 M 29 B 30 B 1 F 2 F 3 F 4 F 5 F 6 F 7 F 8 F 9 E 31 A 32 A 34...

Страница 16: ...nsure you are not over firing your appliance and it will also ensure you are burning fuel at a rate that is most efficient Place a stove thermometer on the top of the appliance Monitor the temperature...

Страница 17: ...ensure uninterrupted blower operation For example a small fire may require a slower blower speed to keep the heat output by the blower consistent If the blower is operated in manual mode it may be ne...

Страница 18: ...ool down to 275 to 400 degrees on Elites locate thermometer on the face of the insert just above the door Now load the firebox and set the draft control At this point you may need to burn the stove wi...

Страница 19: ...pulling up while holding the op posite side of the door Lift door out of the lower hinge pin and place face down on a soft surface Step 2 Remove Door Back Screws 6 ea Using a 5 32 allen wrench remove...

Страница 20: ...lass on Page 19 SMOKES WHEN 1 If smoke is entering the room check to make sure your baffle boards are properly installed DOOR IS OPEN and that the baffle blankets are pushed back flush with the front...

Страница 21: ...fle assembly DO NOT Close the door tightly during Burn In Period DO Be sure to clean any fingerprints from optional accessories that have plated surfaces before burning the appliance Clean the plated...

Страница 22: ...astener Kit 23 71117 Bottom Heatshield 24 H5662 Cascade Olympic Leg Kit Outside Air Plenum Box Contact an IHP dealer to obtain any of these parts Never use substitute materials Use of non approved par...

Страница 23: ...NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE Replacement Parts Model ST310 34 47 48 49 33 35 41 41 39 39 39 42 39 39 39 39 39 39 39 39 39 39 38 37 41 41 39 39 39 42 36 43 45 43 44 39 39 44 40 40 46 40...

Страница 24: ...24 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE Replacement Parts Model ST310 Door Parts Blower Parts 25 29 31 28 27 26 32 30 7 11 10 6 9 5 4 4 1 8 2 3...

Страница 25: ...25 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE Replacement Parts Model ST310 22 24 18 20 21 23 Leg and Leg Parts...

Страница 26: ...26 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE Replacement Parts Model ST310 15 18 15 18 19 16 17 19 Ash Drawer Pedestal and Pedestal...

Страница 27: ...DLE AND NAMEPLATE F1870 TRAD FPK BG LG Large Traditional Faceplate Kit Brushed Gold F1869 TRAD FPK G LG Large Traditional Faceplate Kit Gold BLOWER H7917 BLWR FSB700 SS Blower Kit FS Woodstoves OUTSID...

Страница 28: ...28 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE SAFETY LISTING LABEL eNGLISH 2013 2014 2015 Innovative Hearth Products LLC 1502 14th St NW Auburn WA USA 98001...

Страница 29: ...29 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE SAFETY LISTING LABEL FRENCH Innovative Hearth Products LLC 1502 14th St NW Auburn WA USA 98001...

Страница 30: ...30 NOTES...

Страница 31: ...a binder may burn at excessive temperatures and may cause damage to the Product or may cause it to function improperly IHP stoves inserts and high efficiency EPA fireplaces are approved for burning d...

Страница 32: ...ment parts See Pages 22 through 26 for a complete replacement parts list Use only parts supplied from the manufacturer Normally all parts should be ordered through your IHP distributor or dealer Parts...

Отзывы: