ELECTRICAL AND OPERATING INSTRUCTIONS  

 
General Requirements 
 

 

 
Turn the heater on only when you need heat and avoid any misuse.  
Do not use the heater if the ambient temperature exceeds 80°F (25°C). 
Before connecting the appliance make sure that the voltage is the same as 
indicated on the device and the line supply is corresponding to the relevant 
electrical code. 
 

 
 
1.  The installation should always be carried out by a qualified electrician in accordance with the relevant electrical 

code: in USA, National Electrical Code, NFPA 70; in Canada, Canadian Electrical Code, Part 1, C22.1. 

2.  The energy supply to the heater must always be properly grounded. 
3.  The appliance is equipped with a junction box.  
4.  For a correct installation of the heater it’s necessary to set the unit with a fused switch or circuit breaker. 
5.  When required by the installation code, to prevent serious harm from an ongoing electric shock, a Ground Fault 

Circuit Interrupter (GFCI) with rated earth leakage operation not exceeding 30mA must be fitted upstream on 
the supply line. Additionally, for ensuring a total disconnection of the unit with a full interruption of the contacts 
in all poles, it’s necessary to install a category III combined circuit breaker with contact opening distance of at 
least 3 mm. 
 
 

 

 

 

 

Additional Information 
 

1.  For supply connections, use wires suitable for at least 167°F (75°C) with the section AWG16. Use copper wire 

only. 

2.  Do not turn the heater on if it’s placed or lying down on any surface. 
3.  The color of the radiator could change from dark black to faded black when used inside smoky or polluted 

environments or at an ambient temperature above the 80°F (25°C). Such a color variation does not interfere 
with the functionality of the heater. 

4.  A safety clearance 40“ (100cm) should always be maintained in front of the heaters. 
5.  The heater is not equipped with a power cord. 
6.  Keep the combustible material away from the heater. 
7.  There are no serviceable parts inside the heater. 
 

 

 

Содержание EW15L12

Страница 1: ... wiring comprise the basic information needed to complete the installation These criteria must be thoroughly understood before proceeding Only personnel who have been trained and understand all applicable codes should undertake the installation Manufacturer representatives are Factory Certified in the service and application of this equipment and can be called on for helpful suggestions about inst...

Страница 2: ...accordance with local codes or in the absence of local codes the National Electrical Code NFPA 70 or the Canadian Electrical Code Part 1 C22 1 The eWAVE heater is designed and manufactured for residential commercial heating applications for indoor and outdoor use according to the Standard for Fixed and Location Dedicated Electric Room Heaters UL 2021 and the Canadian Standard for Electric Air Heat...

Страница 3: ...ONS CAUTION High temperature risk of fire keep electrical cords drapery furnishings and other combustibles at least 3 feet 0 9 m from the front of the heater and away from the side and rear 1 This appliance is intended solely for use as an infrared heater and should not be used for other purposes The manufacturer is not responsible for any damage that could happen for improper use 2 After unpackin...

Страница 4: ...ious harm from an ongoing electric shock a Ground Fault Circuit Interrupter GFCI with rated earth leakage operation not exceeding 30mA must be fitted upstream on the supply line Additionally for ensuring a total disconnection of the unit with a full interruption of the contacts in all poles it s necessary to install a category III combined circuit breaker with contact opening distance of at least ...

Страница 5: ...ature 4 Building materials with low heat tolerance i e plastics vinyl siding canvas tri ply etc may be subject to degradation at lower temperatures It is the installer s responsibility to ensure that adjacent materials are protected from deterioration Some parts of this product can become very hot and cause burns Particular attention has to be given where children and vulnerable people are present...

Страница 6: ... fixed to the wall or to the ceiling by means of the provided supports Ensure that the wall where you intend to install the heater is solid and that no electrical cables or water pipes pass behind it 1 Drill four holes in the wall as shown in the picture 2 Fix two supports on the wall using the proper mounting hardware not included ...

Страница 7: ...upplied screw and bolt 5 Fix the brackets in position by tightening the safety screws 6 Tilt the heater until you can insert a screw in the hole Now the junction box is easy to access 7 Connect the power according to the following diagram 8 After finishing the wiring and closing the junction box cover tilt the heater in the desired angle and insert the bracket screws in the matching holes ...

Страница 8: ...s eWAVE Page 8 LT286 April 09 2020 9 Once the wiring is completed close the connection box with the appropriate screws making sure to position the gaskets between the box and the cover as shown in the figure ...

Страница 9: ...by the user and not by unsupervised children 1 It is important that eWAVE units are regularly cleaned to ensure long and efficient operating life 2 To clean use a soft damp cloth and then dry thoroughly 3 Make sure all parts are dry before powering the heater 4 eWAVE units should be cleaned and inspected every 3 months 5 Avoid the use of harsh detergents solvents and abrasive or aerosol cleaners a...

Страница 10: ...eWAVE Hanging Brackets Kit Part ES314 Item Description Quantity 1 Heater Bracket 2 2 Wall Bracket 2 3 M4x10mm Phillips Pan Scr S S 8 4 M4 Nut S S 4 eWAVE Junction Box Lid Gasket Kit Part ES315 Item Description Quantity 1 Lid 1 2 Gasket 1 3 Screws 2 4 Washers 2 ...

Страница 11: ...anty obligation or liability Provision of this warranty is subject to The eWAVE product must be installed in accordance with the installation instructions and relevant electrical standards and codes The eWAVE product must be maintained and cleaned according to instructions detailed in the installation manual Discoloration of the surface may occur after a period of time this does not constitute a w...

Страница 12: ...Series eWAVE Page 12 LT286 April 09 2020 THIS PAGE LEFT INTENTIONALLY BLANK ...

Отзывы: