Network parameters settings is defined by the first paragraph. It is not
necessary to describe IP address, subnet mask, gateway, DNS, Device
name and Location. To use a range of IP address assigned automatically,
select DHCP server. After a succesful obtaining, these details will appear
below this option, left of the static data.
•
NTP server, domain name server for the current time together with the
definition of time zone. The device has an internal timer that even in
case of connection failure maintains current system time. However, for
proper function and display the current time after restart of the device is
necessary proper and functional setting of NTP server. The device will
then self-correct and update.
•
User name, Login password – username to log-in security via HTTP.
•
Except - exceptions – When selected, authentication wil not be required
for the said HTML pages. It is possible to this way password protect the
device configuration only. Main page with the values remain available to
everyone.
•
HTTP port – Port of the HTTP protocol
•
Sensor unit - sensor units that appear in the history of the data and also
convert.
•
Sensor 1/2 ID, sensor ID, by default 0 for DS18B20. For other types is
mentioned in the application data sheet for a given sensor, such as
relative humidity sensor 1, etc.
•
SNMP, option for reading and setting-up values using SNMP v.1.0
protocol. TRAP IP address is a destination address, where is sent
potential TRAP packet to.
•
Output control event. In case of meeting any of the conditions of the
"set output"
option, it will change the status of the output relay
according to setting and a TRAP packet will be sent. In case that is
chosen only TRAP, only this ALERT TRAP will be sent, if meeting set
conditions without changing the status of the output relay. The relay can
then be controlled only by using the SNMP or manually through the web
or the button.
•
Hysteresis - Hysteresis with an accuracy of 0.1 degrees, 2.0 represents a
dero - 1 ° C from the set temperature in menu
Set output
. It's
valid for any value of the sensor, not only for temperature.
•
SNMP SET reswitch time – restart time for a short-term flip of the output
relay when using SNMP SET - SET relay to reswitch time. For both
outputs is identical.
•
OUTPUT1/2 after start – the state of a relay output after switching power
supply or restarting the device. NC - terminals C and NC connected, NO
terminals C and NO connected, REM - connected terminals according to
the last known state