RACK TOWER ONLINE UPS
4.011.2017
RTS-ON-user-manual_ENG-R1
29
120V
100/110/115/120/127VAC Setting available via LCD
Output PF
0.8
/
0.9
0.8/0.9
0.8/0.9
0.8/0.9
Output power(Watt)
800/900
1200/1350
1600/1800
2400/2700
Inverter overload capability
105%
~
150%: transfer to bypass mode after 30s giving alarm;
>
150% : transfer to bypass mode after 300ms giving alarm;
Voltage accuracy
±
1%
Load crest
3:1
From AC mode to BAT mode
0ms(transfer time)
From BAT mode to AC mode
0ms(transfer time)
Efficiency
Line
mode
≧
90 %
B
AT
mode
87%
ECO mode
9
4
%
Output frequency
Under Mains mode
Same as input frequency
Under battery mode
(
50/60±0.2
)
Hz
Phase-locked rate
≤1Hz/s
Total voltage harmonic
distortion
Full linear load< 3%
;
Full nonlinear load< 5%
Battery
Battery type
Sealed lead acid maintenance free battery
Quantity
2
3
4
4
6
6
8
DC voltage
24V
36V
48V
48V
72V
72V
96V
Inbuilt battery
9AH/12V
7AH/12V
9AH/12V
9AH/12V
7AH/12V 9AH/12V
7AH/12V
Output voltage
27.
1
±0.4
V 40.6
±
0.5V
5
4.2
±0.6
V
5
4.2
±0.6
V
8
1
.
3
±0.9
V
8
1
.
3
±0.9
V 108.4
±
1V
Back up time
Based on battery capacity
Charge method
Three-stage charging
Charge current
Standard model
:
1A
Long time model
: 6A
System Control and Communication
Function
Silence; cold start; AC restart; Auto restart.
Protection
Over-temp protection;
Fan testing protection;
AC L and N reversely connecting protection;
Output short circuit protection
Communication port
RS232; SNMP card; USB