RACK TOWER ONLINE UPS
4.011.2017
RTS-ON-user-manual_ENG-R1
15
any more. The “ON” letter will flash. Press and hold the inquiring key (
,
)
for more than half a second
(less than 2 seconds) to determine whether the BPS function is used or not. If used, the corresponding word is
“ON”, if not, the word is “OFF”. It can be determined by yourself.
③
Confirm the Bypass output setting interface. After selecting ON or OFF, press and hold the function setting key
for more than half a second (less than 2 seconds), Now, the BPS setting function is completed and the
“ON” or “OFF” will light without flash.
④
Press and hold the function setting key
for more than 2 seconds, exit from the setting interface and return
to main interface.
⑤
After setting BPS ON, without turning on the UPS whatever mains power being plugged in or not, there is
bypass output but no backup function.
2 5 %
5 0 %
7 5 %
1 0 0 %
2 5 %
5 0 %
7 5 %
1 0 0 %
ST
DB
Y
2 5 %
5 0 %
7 5 %
1 0 0 %
2 5 %
5 0 %
7 5 %
1 0 0 %
ST
DB
Y
4.6
.3 Output voltage setting
①
Enter the setting interface. Press and hold the function setting key
for more than 2 seconds, then come to
setting interface, press and hold the inquiring key (
,
)
for more than half a second(less than 2 seconds),
select the function setting, choose output voltage setting interface, at the moment, the letters “OPU” will flash.
②
Enter the output voltage setting interface. Press and hold the function setting key
for more than half a
second(less than 2 seconds), then come to setting interface of output voltage OPU, at this time, the letters “OPU”
will not flash any more. The numerical value next to the OPU will flash. Press and hold the inquiring key (
,
)
for more than half a second (less than 2 seconds), select the numerical value in accordance with “OPU”
function. The provided voltages are 208V, 220V, 230V, 240V or 100V, 110V, 115V, 120V, 127V, you can choose
anyone by yourself (The default value is 220V or 120V).
③
Confirm the output voltage setting interface. After selecting numerical value, press and hold the function setting
for more than half a second (less than 2 seconds). Now, the OPU setting function is completed and the
numerical value will light without flash.