3PH ON-GRID solar inverter
11
www.ips-ups.eu
IPSPV33-ONGI-manual_ENG-R0
7.10.2020
4.2 Mounting the Inverter
4.2.1 Clearance
Note: Only install the inverter vertically or tilted backwards no more than 15 degrees. Do
not tilt or install the inverter horizontally. The wiring terminal should be downwards.
In order to maintain sufficient ventilation, when installing the inverter a minimum
clearance of 30 cm at the sides and 50 cm at the top must be maintained. Operation
and reading are made easier by installing the inverter with its display at eye level and by
keeping a distance of 100 cm from the front. All cables are routed to the outside through
the underside of the enclosure, therefore a minimum clearance of 50 cm must be
observed here.
4.2.2 Installation Procedure
1. Place the wall mounting bracket against a suitable wall for mounting and align using a
level. Mark the position of the drill holes using the wall mounting bracket.
2. Drill holes on the markings for them.
3. Secure the wall mounting bracket to the wall using expansion screws. Tighten the
screws with a minimum torque of 30Nm, and M6 x 50 expansion bolts are
recommended for use.