background image

manual pressure sensor 

page 3 

ipf electronic gmbh

 

Kalver Str. 25 - 27 

58515 Lüdenscheid - Germany

Subject to alteration!

Tel  +49 2351 9365-0

Fax +49 2351 9365-19

safety instructions 

www.ipf-electronic.com 

[email protected]

Read the product description before installing the unit. Ensure that the 

product is siutable for your application without any restrictions. 

Non-adherence to the operating instructions or technical data can lead to 

personal injury and/or damage to property. 

In all applications check compliance of the product materials (see technical 

data) with the media to be measured. 

Do never touch the pressure membrane with the fingers or any other object. 

The membrane can be damaged irreparably! 

Never use these articles in applications where the safety of a person 

depends on their functionality!

Содержание DW34312 Series

Страница 1: ... sensor page 1 ipf electronic gmbh Kalver Str 25 27 www ipf electronic com Subject to alteration 58515 Lüdenscheid Germany Tel 49 2351 9365 0 Fax 49 2351 9365 19 info ipf electronic com manual pressure sensor DW34312x ...

Страница 2: ...6 page 8 page 8 page 9 page 9 page 10 page 11 page 12 page 12 page 15 page 16 page 17 description of the operating elements menu overview operation modes of the switching outputs switch point with release position switch point with hysteresis window function with release position window function with hysteresis operating modes programming list of parameters mounting and electrical connection initi...

Страница 3: ...t is siutable for your application without any restrictions Non adherence to the operating instructions or technical data can lead to personal injury and or damage to property In all applications check compliance of the product materials see technical data with the media to be measured Do never touch the pressure membrane with the fingers or any other object The membrane can be damaged irreparably...

Страница 4: ...lights if the output is switched 3 LED red S2 displays the switching state of output 2 lights if the output is switched 4 programming button Enter Set selection of menus and parameters setting and saving of parameters Enter Set Enter Set 5 arrow key up setting the parameter values increasing the value fast keep the button pressed stepwise by pressing the button short 6 arrow key down setting the p...

Страница 5: ...ng in PROGRAMM mode saving current value after pressing Enter Set button The indication on the display depends on the programmed function If one of these functions is selected in the enhanced Menu the indication will be shown on the display program button Enter Set symbol Enter Set Enter Set Selection of menus and submenus as well as confirming and saving of parameter values Short pressing in the ...

Страница 6: ...ackwards inside the menu and parameters without saving the settings In order to leave all menus and submenus please press the ESC button again and again until you are back in the RUN mode key lock If the device is in the RUN Mode and you press the arrow keys at the same time for at least 5 seconds the key lock will be activated The display shows sLOC blinking 3 times Now the adjusted settings can ...

Страница 7: ...ual pressure sensor page 7 ipf electronic gmbh Kalver Str 25 27 58515 Lüdenscheid Germany www ipf electronic com Subject to alteration Tel 49 2351 9365 0 Fax 49 2351 9365 19 info ipf electronic com 2 level ...

Страница 8: ...nal pressure stated by the system The smallest adjustable hysteresis is 1 of the nominal pressure stated by the sys tem All examples are effective for output 2 if this output is defined as switching output SP 2 also switch point with release position programmed parameters SP 1 250 0 bar rP 1 40 0 bar output release position switch point pressure bar An increasing pressure up to SP 1 e g 250bar swi...

Страница 9: ...ammed parameters SP 1 50 0 bar HYS 1 20 0 bar output pressure bar switch point An increasing pressure up to SP 1 e g 50bar switches the output according to the ad justed switching function no or nc This state remains also for higher pressure For decreasing pressure the switching state changes after passing the hysteresis e g 20bar If SP 1 will be changed the hysteresis HYS1 remains the same that i...

Страница 10: ...page 10 manual pressure sensor ipf electronic gmbh Kalver Str 25 27 58515 Lüdenscheid Germany www ipf electronic com Subject to alteration Tel 49 2351 9365 0 Fax 49 2351 9365 19 info ipf electronic com ...

Страница 11: ... value Pressing the arrow key downwards or upwards briefly changes the parameter value step by step Pressing the arrow key continuous changes the value fast Pressing the Enter Set button safes the adjusted value the display blinks three times The unit now operates with the new adjusted value Returning to the RUN Mode Press the ESC button enhanced menu programmimg mode Setting of the parameter valu...

Страница 12: ...description Enter Set Enter Set 1X SP1 Press the Enter Set button briefly to get into the main menu Press the Enter Set button again The current value for switch point S1 will be displayed Set the parameter value with the arrow keys Confirm the set value with the Enter Set button 1X rP1 HYS1 Press the Enter Set button The current value for the release position S1 respectively the hysteresis will b...

Страница 13: ...witching function is set off delay timer function S1 Ou 2 Configuration output 2 Four switching functions the error signal or 4 analog functions are possible SP HY switch point hysteresis SP rP switch point release position FE HY window function hysteresis FE rP Err 2 window function release position error signal oFF 2 output 2 off noc 2 noc 2 is only active if Ou 2 is set as switching function Fu...

Страница 14: ...e of the system The lowest value is displayed delete memory CYC counter switching cycles of S COF zero point calibration The internal measurand operating value of the sensor is offset compared to the real measurand adjustment range 10 of the measuring span ddIS Damping of the display Peak Hold Time FdIS Dislpay functions rd rotate display Ph peak hold Temporary display of peak values Rd Ph rotate ...

Страница 15: ...parameters to be set and ad justed by a PC or notebook The suitable interface cable and Windows Software can be ordered with the article number AD000011 With the Software you are able to adjust all functions described above NOTE Use a shielded cable socket e g VK205A21 in order to avoid interfer ences mounting and electrical connection Before mounting and removing the unit Make sure that no pressu...

Страница 16: ...m pressure is lower than the measuring range SC1 short circuit S1 analog output error signal check wiring check load of S1 SC2 short circuit S2 analog output error signal check wiring check load of S2 SC short circuit S1 and S2 analog output error signal check wiring check load ERR sensor defect internal error S1 and S2 are switched off analog output error signal contact manufacturer AO if current...

Страница 17: ...ure drift conn to pressure system sensor head material housing material degree of protection electrical connection optical interface see list of articles 150 of nominal pressure PN peak value memory every 2msec display via PC 12 32V DC reverse polarity protection 15 32V DC if operated with voltage output 2V 60mA 2 x pnp switching no nc 1A short circuit protection 0 to 20sec on off delay adjustable...

Страница 18: ... 2x1A M12 conn4pin 2 DW343124 34 G1 2A 100bar stainless steel polyester V4A 12 32V DC pnp no nc analog 2x1A M12 conn4pin 2 DW34312G 34 G1 2A 200bar stainless steel polyester V4A 12 32V DC pnp no nc analog 2x1A M12 conn4pin 2 DW343126 34 G1 2A 400bar stainless steel polyester V4A 12 32V DC pnp no nc analog 2x1A M12 conn4pin 2 DW343127 34 G1 2A 600bar stainless steel polyester V4A 12 32V DC pnp no n...

Отзывы: