BMA_77024-o16m-05_Rev2_en
IPAS GmbH, Hölscherstraße 27, D-47167 Duisburg
Operating- and mounting instructions
PowerBlock o16 Multi
Order number: 77024-180-05
General usage
Power Block series consists of 4 different devices types. It can be
installed in a standard distribution board.
only 4 DIN Rail modules for 4 outputs and 6 inputs
only 4 DIN Rail modules for 8 outputs
(Binary/Shutter/Blind/Fan Coil)
only 8 DIN Rail modules for 16 outputs
(Binary/Shutter/Blind/Fan Coil)
A brief overview of the functionality is given in the following table:
Device type and accessories
At present the following device types are available in the PowerBlock
control group:
Product
Description
Order number:
PowerBlock o8
8 capacitive outputs
77024-180-01
PowerBlock o8m
8 capacitive outputs
77024-180-04
PowerBlock o16
16 capacitive outputs
77024-180-02
PowerBlock o16m
16 capacitive outputs
77024-180-05
PowerBlock io64
4 capacitive o
6 analog / digital inputs
77024-180-03
InBlock
8 x 230VAC inputs
7704-180-30
Scope of delivery
The following individual components are included in the delivery of the
PowerBlock device:
-
Complete device with connected bus connector
-
Operating and mounting instructions
-
1x heat shrinkable tubing 1.2 x 2cm for additional insulation
of the bus cable
-
Delivered in break-proof individual packaging
Application programs
The following application programs are currently available for the
PowerBlock device:
-
77014-PowerBlock o16m-22-0110
Installation device
Risk of death by electric shock.
The device is intended for interior installation in dry rooms.
The device must only be installed and commissioned by an
accredited electrical engineer.
When planning and construction of electrical installations, the
national guidelines, rules and regulations of the country in quest-
ions are to be obeyed, as well as all current KNX guide lines.
For the installation the device must be switched to zero potential.
The device must not be opened.
Any faulty devices are to be sent together with a return delivery
to the manufacturer.
Technical data
POWER AND OUTPUTS SPECIFICATIONS
Power supply
Supply Voltage:
Max. Consumption:
Additional power
supply:
21..30VDC
9,4mA
No
Number of
outputs
Contacts:
16 Dry contact
(potential-free)
Output
configuration
Up to 16 outputs
Up to 8 channels
Up to 4 Fan Coil
controllers
Output nominal
values
AC rated current /
voltage:
DC rated current /
voltage:
16A / 250VAC 50/60Hz
C-Loads max. = 140 µF
16A / 30VAC
Device nominal
values
Current / Voltage
16A /250VAC per Output
Phases switching
distribution
1 independent phase
allowed per output
Output life
expectance
Mechanical:
Electrical:
3𝑥10
operations (at 60
times/min)
4𝑥10
cycles with
resistive load at maximal
current
Connections
KNX bus connection
terminal:
Terminal screw block:
Tightening torque for
terminal screw:
0,8 mm Ø solid
max. 6 mm Ø solid
maximum 0.6 Nm
GENERAL SPECIFICATIONS
Control and
display elements
Programming button:
LED, red:
16 x buttons: (for
manual channels
control)
16 x LEDs, red:
To assign the physical
address.
Displays addressing mode
To switch On/Off outputs /
Move Up/Down channels /
Select Fan Speed / switch
valve output.
To display actual
outputs/channels status
Outputs
BINARY (POWER LEDs
SUPPORTED)
SHUTTER / BLIND
Bus failure
Bus failure
Central ON/OFF
Counters
Scenes
Timers
Alarms
Disable function
Manual control
Scenes
Presets
Alarms
Disable function
Manual control
Façade control
Shutter slits control
True height positioning for
shutter/blind
ADVANCED FUNCTIONS
FAN COIL (FC)
Analog & digital alarms
Fan Auto/Manual
Scene controler
Timers (with cyclic sending of
time remaining
Overwrite end user parameters
Logic functions
Setpoints
Behaviour at bus recovery
Operation modes (Fan & Valve
restrictions)
Manual fan speed with multiple
DPTs obj.
Remaining time to change filter
Fan speed timers/delays/cyclic
Scenes and Day & Night object
Purge valve
Thermostat monitoring
Alarms