background image

Page 2

SPECIFICATIONS - 

Illustration 1

Model

ILBLP CP10

ILBLP CP15

Output Voltage (Min - Max)

15-55 VDC

20-55 VDC

Minimum Operation

90 Minutes

90 Minutes

Input Voltage (Min - Max)

120-277 VAC

120-277 VAC

INSTALLATION INSTRUCTIONS

CAUTION:   Before installing, make certain A.C. power is off and the Threaded Body Test Switch (TBTS) is disconnected.

STEP 1 - 

MOUNTING THE ILBLP CP HE SD

The 

ILBLP CP HE SD

 is designed to be installed inside the 

luminaire channel or wireway. Place the unit on the luminaire 

mounting surface and fasten through the 

ILBLP CP HE SD 

mounting slots using serrated head screws (U3840).

STEP 2 - 

WIRING TO THE LED LOAD AND NORMAL DRIVER

ILBLP NORMAL DRIVER AND LED LOAD CONNECTIONS

ilblp_tbts_normal-driver-and-load-only.eps

AC (NORMAL) 

DRIVER

IOTA ILBLP

EMERGENCY DRIVER

LED

LOAD

WHITE

WHT/RED
OR RED/WHT

RED (+)
BLUE (-)

YELLOW
BROWN

LEDCODE (+)
LEDCODE (-)

VIOLET/WHITE (+)

 LED INPUT(-)

 LED INPUT (+)

 LED OUTPUT (+)

 LED OUTPUT (-)

!

Cap unused  

LEDCODE wires

Refer to the appropriate wiring diagram below. Make sure all connections are in accordance with NEC and any other 

 

local requirements.

CHANNEL COVER

TBTS

EMERGENCY

DRIVER

LUMINAIRE HOUSING

TBTS NUT

STEP 3 - 

INSTALLING THE THREADED BODY TEST SWITCH (TBTS)

A.  Locate a suitable location for the TBTS and 

cable that is visible outside the fixture. Drill 

or punch a 1/2” diameter hole in the fixture 

wall or wireway cover. Insert the TBTS into 

the hole so that the LED test button/pilot 

light is located outside of the fixture. 

B.  Secure the TBTS using the 

TBTS nut.

C.  Connect and fully engage the TBTS 

Connector to the TBTS Socket. Ensure 

the TBTS Connector is properly seated 

in the TBTS Socket, then mark the TBTS 

location on the fixture with the TBTS Label 

and apply the SD Status Indicator Sticker. 

Remote Mounting

 - The TBTS may be remote mounted from the fixture up to 25 feet. 

Before extending the TBTS wires, 

ensure that AC Power is off and the TBTS has been disconnected.

 To extend the TBTS wires, splice the TBTS leads 

between the test switch and connector and install a patch cable (minimum 18 AWG) of the desired length to the spliced ends. 

Be sure to observe wire color. After extending the TBTS wires, follow the installation procedure (steps A, B, and C) above to 

recconnect the TBTS.

Содержание ILBLP CP10

Страница 1: ...rvicing should be performed by qualified personnel only De energize before opening 6 The ILBLP CP HE SD is for use with grounded LED luminaires listed to UL standards Not for use in heated air outlets...

Страница 2: ...are in accordance with NEC and any other local requirements CHANNEL COVER TBTS EMERGENCY DRIVER LUMINAIRE HOUSING TBTS NUT STEP 3 INSTALLING THE THREADED BODY TEST SWITCH TBTS A Locate a suitable loc...

Страница 3: ...e unit to charge for at least 1 hour before performing a functional test B Verify that the TBTS light is on The lamp will illuminate Red while the battery is charging and Green when the battery is ful...

Страница 4: ...by the authority having jurisdiction SERVICING SHOULD BE PERFORMED BY QUALIFIED PERSONNEL Consult Customer Service or visit www iotaengineering com for current warranty information Load Calibration T...

Страница 5: ...ar du personnel qualifi Mettre hors ten sion avant de l ouvrir 6 L ILBLP CP HE SD est con u pour tre utilis avec des luminaires DEL mis la terre homologu s UL Ne pas utiliser avec des prises d air cha...

Страница 6: ...TIER DU LUMINAIRE CROU DU TBTS TAPE 3 INSTALLER LE COMMUTATEUR DE TEST DU CORPS FILET TBTS A Trouvez un emplacement satisfaisant pour le TBTS et le c ble qui est visible l ext rieur du luminaire Perce...

Страница 7: ...de l alimentation secteur fait fonctionner le module DEL comme pr vu L ILBLP CP HE SD est en mode de chargement en veille Le TBTS est allum et indique de mani re visuelle que la batterie est en cours...

Страница 8: ...e module DEL s teigne M thode 2 D branchez le TBTS Une fois que toutes les sources d alimentation sont d branch es du luminaire ILBLP CP HE SD et du luminaire d urgence proc der l entretien requis Une...

Отзывы: