ILB-LP INPUT WIRING

ilbcp_tspl_input

IOTA ILBLP

EMERGENCY DRIVER

WHITE

NEUTRAL

UNSWITCHED

24/7 POWER

BLACK (120 TO 277V, 50/60HZ)

STEP 4 - 

WIRING THE AC INPUT

The 

ILBLP CP HE SD HV

 requires an 

unswitched AC input 

of 120/277 volts. Connect the 

BLACK 

wire to the 

120/277 Line

and the 

WHITE 

wire to the 

Neutral

CAUTION: The case be grounded.

COMPLETING INSTALLATION

STEP 5 - 

APPLY AC POWER

A.  

Apply continuous AC power to the unit, and allow the unit to charge for at least 1 hour before performing a 

functional test

.

B.  Verify that the TBTS light is on. The lamp will show Red for low battery and Green for sufficient battery charge.
C.  Press and hold the TBTS button for two seconds. The pilot light will blink. Within five seconds, the LED Module should be 

operating at a reduced light output.  The test mode runs for 30 seconds.  To exit the test mode earlier, press and hold the 

TBTS button for two seconds.  If the LED Module in the fixture returns to normal operation, the unit is ready for normal and 

emergency service. If not, see the Troubleshooting section.

OPERATION

Normal Mode

 

A.C. power is present. The A.C. Driver operates the LED Module as intended. The 

ILBLP CP HE SD HV

 is in the standby 

charging mode. The 

TBTS 

will be lit providing a visual indication that the battery is being charged.

Emergency Mode

 

The A.C. power fails. The 

ILBLP CP HE SD HV

 senses the A.C. power failure and automatically switches to the 

Emergency 

Mode

. The LED Module is illuminated, at reduced output, for a minimum of 90 minutes. When the A.C. power is restored, the 

ILBLP CP HE SD HV

 switches the system back to the 

Normal Mode

 and resumes battery charging.

TROUBLESHOOTING

Problem

Possible Cause

Emergency LED Module does 
not operate when the TSPL 
Button is pressed.

TSPL Charging LED 
not on

Fixture does not operate in the 
Normal Mode

1. Incorrect wiring of the Emergency Driver and/or AC Driver.
2. The LED Module is not compatible with the Emergency Driver.
3. Battery has not charged for at least one hour.
4. TSPL is not inserted properly into the Emergency Driver socket.
5. The wrong test accessory is being used.

1. AC Power is Off
2. TSPL is not inserted properly into the Emergency Driver socket.
3. The wrong test accessory is being used.

1. Battery is not fully charged.
2. The LED Module is not within the Emergency Driver specifications.
3. Battery is at end of life.

1. Incorrect wiring of the Emergency Driver and/or AC Driver.
2. AC power is off to the AC Driver.

Emergency Driver does not 
operate lamps in the emergen-
cy mode for at least 90 minutes.