CAUTION: Before installing, make certain A.C. power is off and the Threaded Body Test Switch
(TBTS) is disconnected.
STEP 2 -
WIRING TO THE LED LOAD AND NORMAL DRIVER
STEP 1 -
MOUNTING THE ILBLP CP HE SD HV
STEP 3 -
INSTALLING THE THREADED BODY TEST SWITCH (TBTS)
The ILBLP CP HE SD HV should be mounted on or nearby the
fixture above the ceiling. The flex conduit should be wired into
the driver/lamp compartment or to an electrical junction box on
the fixture which allows access to the fixture connections.
A. Locate a suitable location for the TBTS
and cable that is visible outside the fixture.
Drill or punch a 1/2” diameter hole in the
luminaire wall or wireway cover. Insert the
TBTS into the hole so that the LED test
button is located outside of the fixture.
B. Secure the TBTS against the
luminare housing by screwing
on the TBTS nut.
C. Connect and fully engage the TBTS
Connector to the TBTS Socket.
Ensure the TBTS Connector is
properly seated in the TBTS Socket,
then mark the TBTS location on
the switch box plate with the TBTS
Label and apply the SD Status
Indicator Sticker.
INSTALLATION INSTRUCTIONS
Refer to the appropriate wiring diagram below. Make sure all connections are in accordance with NEC and any other
local requirements.
ILB-LP NORMAL DRIVER AND LED LOAD CONNECTIONS
ilbcp_tspl_normal-driver-and-load-only.eps
AC (NORMAL)
DRIVER
IOTA ILB-LP
EMERGENCY DRIVER
LED
LOAD
WHITE
WHT/RED
RED (+)
BLUE (-)
YELLOW
BROWN
LEDCODE (+)
LEDCODE (-)
VIOLET/WHITE (+)
LED INPUT(-)
LED INPUT (+)
LED OUTPUT (+)
LED OUTPUT (-)
!
Cap LEDCODE wires
if unused
TBTS
LUMINAIRE HOUSING
ILB-LP-CP-HE-SD-HV
FLEX
CEILING
TILE
LED DRIVER AND ARRAY
COMPARTMENT
TBTS
Lorem ipsum
TBTS
ILB-LP-CP-HE-SD-HV
SPECIFICATIONS -
Illustration 1
MODEL
OUTPUT POWER
(CONSTANT)
MAX. CHARGE
AMPS
OUTPUT VOLTAGE
(MIN-MAX)
BATTERY
AMPS, MAX
CP10
CP15
10 WATTS
15 WATTS
0.213
0.211
15 - 55
20 - 55
1.20
1.04
0.08
0.09
0.10
0.11
NORMAL OPERATION
EMERGENCY OPERATION
INPUT AMPS
120 VAC
277 VAC
0.209
55-200
1.5
1.5
55-250
0.019
20 WATTS
CP20
CP30
30 WATTS
0.039
0.211
0.027
0.055
LUMINAIRE HOUSING
TBTS NUT
TBTS NUT