CAUTION:   Before installing, make certain A.C. power is off and the Threaded Body Test Switch 

(TBTS) is disconnected.

STEP 2 - 

WIRING TO THE LED LOAD AND NORMAL DRIVER

STEP 1 - 

MOUNTING THE ILBLP CP HE SD HV

STEP 3 - 

INSTALLING THE THREADED BODY TEST SWITCH (TBTS)

The ILBLP CP HE SD HV should be mounted on or nearby the 

fixture above the ceiling. The flex conduit should be wired into 

the driver/lamp compartment or to an electrical junction box on 

the fixture which allows access to the fixture connections.

A.  Locate a suitable location for the TBTS 

and cable that is visible outside the fixture. 

Drill or punch a 1/2” diameter hole in the 

luminaire wall or wireway cover. Insert the 

TBTS into the hole so that the LED test 

button is located outside of the fixture. 

B.  Secure the TBTS against the 

luminare housing by screwing 

on the TBTS nut.

C.  Connect and fully engage the TBTS 

Connector to the TBTS Socket. 

Ensure the TBTS Connector is 

properly seated in the TBTS Socket, 

then mark the TBTS location on 

the switch box plate with the TBTS 

Label and apply the SD Status 

Indicator Sticker. 

INSTALLATION INSTRUCTIONS

Refer to the appropriate wiring diagram below. Make sure all connections are in accordance with NEC and any other  

local requirements.

ILB-LP NORMAL DRIVER AND LED LOAD CONNECTIONS

ilbcp_tspl_normal-driver-and-load-only.eps

AC (NORMAL) 

DRIVER

IOTA ILB-LP

EMERGENCY DRIVER

LED

LOAD

WHITE

WHT/RED

RED (+)
BLUE (-)

YELLOW
BROWN

LEDCODE (+)
LEDCODE (-)

VIOLET/WHITE (+)

 LED INPUT(-)

 LED INPUT (+)

 LED OUTPUT (+)

 LED OUTPUT (-)

!

Cap LEDCODE wires 

if unused

TBTS

LUMINAIRE HOUSING

ILB-LP-CP-HE-SD-HV

FLEX 

CEILING

TILE

LED DRIVER AND ARRAY 

COMPARTMENT

TBTS

Lorem ipsum

TBTS

ILB-LP-CP-HE-SD-HV

SPECIFICATIONS - 

Illustration 1

MODEL

OUTPUT POWER

(CONSTANT)

MAX. CHARGE

AMPS

OUTPUT VOLTAGE

(MIN-MAX)

BATTERY

AMPS, MAX

CP10
CP15

10 WATTS

15 WATTS

0.213

0.211

15 - 55

20 - 55

1.20

1.04

0.08

0.09

0.10

0.11

NORMAL OPERATION

EMERGENCY OPERATION

INPUT AMPS

120 VAC

277 VAC

0.209

55-200

1.5
1.5

55-250

0.019

20 WATTS

CP20
CP30

30 WATTS

0.039

0.211

0.027

0.055

LUMINAIRE HOUSING

TBTS NUT

TBTS NUT