IMPORTANT SAFEGUARDS

READ AND FOLLOW ALL SAFETY INSTRUCTIONS

  1. 

WARNING 

– Dual Power Supply - Risk of shock hazard even if AC power is OFF.

 2. 

WARNING 

 

Disconnect TBTS (Threaded Body Test Switch) connector before servicing fixture.

 3. 

WARNING 

 

DO NOT mount near a gas or electric heater.

  4. 

CAUTION 

– Before wiring to power supply, turn off electricity at fuse panel or circuit breaker.

  5. 

CAUTION 

– Service by Qualified Personnel only. De-energize before opening.

  6. 

CAUTION 

– DO NOT attempt to service the battery. It is not field replaceable.

  7. 

CAUTION 

– DO NOT use outdoors, in air handler heated outlets, or in hazardous locations. This product is for 

use with indoor and damp rated fixtures where the ambient temperature is 0°C minimum to 55°C maximum.

  8. 

CAUTION 

– DO NOT use accessory equipment not recommended by the manufacturer.

  9. 

CAUTION 

– DO NOT use this equipment for other than its intended use.

 10

.  Consult your local building code for approved wiring or installation.

 11. 

The LED Emergency Driver must be connected to an un-switched AC power source of 120 to 277 Vac.

 12.  Product  output voltage varies accorting to wattage. Refer to 

Illustration 1

 for output voltage per model.

13.  Equipment should be mounted in a location and at heights where it will not be readily subject to tampering by 

unauthorized personnel.

 14.  Make sure that the branch circuits are derived from a common phase for both normal lighting LED drivers and 

the LED Emergency Driver 

prior

 to installation.

 15. 

When used with a switched fixture, it is important that the power to the LED Emergency Driver be provided by 

an un-switched circuit.

 16. 

LED Emergency Drivers are for factory and field installation. They are not field serviceable.

 17.  Allow Battery Packs to charge 24 hrs before initial and full-discharge testing.
18.  Emergency lighting system should be tested per all of the required tests and as often as local codes require or 

at least quarterly to ensure all components are operational.

19. 

Lighting fixture manufacturers, electricians, and end-users need to ensure product system compatibility before 

final installation

s.

SAVE THESE  INSTRUCTIONS

ILBLP CP HE SD HV

“S” MOUNTING STYLE

HIGH-EFFICIENCY EMERGENCY

LIGHTING EQUIPMENT 

FOR LED

INSTRUCTION MANUAL