IOTA ILB-CP20-HE-SD-S Скачать руководство пользователя страница 4

Page 4

68D20-119 

REV 1901

Automatic Monthly Testing 

– The 

ILB-CP20-HE-SD-S

 will automatically conduct a 30 second test once every month. If 

the 

ILB-CP20-HE-SD-S

 encounters a problem, the 

TBTS

 will flash 

RED

. See the Table A below for diagnosis.

Automatic Annual Testing

 – The 

ILB-CP20-HE-SD-S

 will automatically conduct a 90 minute test every twelve months.  

If the 

ILB-CP20-HE-SD-S

 encounters a problem, the 

TBTS

 will flash 

RED

. See the Table A below for diagnosis. 

To insure accurate testing, the 

ILB-CP20-HE-SD-S

 will not conduct any scheduled automatic tests or allow for manual  

testing or calibration for a period of up to 24 hours after the unit has discharged, regardless of reason.  This period is 

easily indicated by the 

TBTS 

flashing 

green

.

Failure Diagnosis 

-  The 

ILB-CP20-HE-SD-S

 

is designed to provide a general indication of where a fault in the emer-

gency lighting circuit may be located, based on the flashing failure code indicated by the 

TBTS

.

 

Charge Failure

 - A fault is preventing the 

ILB-CP20-HE-SD-S

 from charging correctly. Please contact Customer  

 Service.
 

Battery Failure

 - The 

ILB-CP20-HE-SD-S

 

battery is unable to fully charge, or was not able to supply sufficient  

 

voltage to the LED load during a test.  Please contact Customer Service. 

 

Load Failure - 

The 

ILB-CP20-HE-SD-S

 

has detected an issue with your LED load or the 

ILB-CP20-HE-SD-S

  

 

internal load transfer. If it can be verified that the LED load is operating correctly, please contact Customer  

 Service. 
Note: in cases of multiple failures only the highest priority failure will be indicated.  Charge Failure is the highest priority 

failure, followed by Battery Failure, followed by Load Failure.

LED IS FLASHING 

GREEN

 WHEN CHARGING, SOLID 

GREEN

 WHEN READY.  FAILURE CODES ARE

INDICATED BY THE 

RED

 LED

CHARGE FAILURE

BATTERY FAILURE

LOAD FAILURE

1 FLASH

2 FLASHES

3 FLASHES

FAILURE CODES OCCUR ONCE EVERY 
15 SECONDS. ONLY HIGHEST PRIORITY
FAILURE IS INDICATED.

CANCEL 90-MINUTE TEST

30-SECOND TEST

90-MINUTE TEST

1 X PRESS AND RELEASE

PRESS AND HOLD

2 X PRESS AND RELEASE

A LOAD CALIBRATION CAN ALSO BE PERFORMED BY DISCONNECTING AND RECONNECTING THE UNIT CONNECTOR

ILB-CP-HE-SD MANUAL TESTING SEQUENCES

LOAD CALIBRATION

1

1

TOGGLE = SWITCHING TO ON STATE OR OFF STATE

2

WALL SWITCH TESTING IS NOT RECCOMMENDED FOR PHASE-DIMMING APPLICATIONS

3

UNIT CONNECTOR MUST BE CONNECTED

4

2

3

4

QUICK TEST

3 X PRESS AND RELEASE

4 X PRESS AND RELEASE

TBTS

TEST TYPE

WALL SWITCH

MINIMUM BATTERY CHARGE REQUIREMENTS

N/A

6 TOGGLES

8 TOGGLES

4 TOGGLES

N/A

2 HOURS

24 HOURS

24 HOURS

24 HOURS

ILB-CP-HE-SD MANUAL TESTING SEQUENCES  -  CANCELLING TEST

TBTS

TEST TYPE

WALL SWITCH

MINIMUM BATTERY CHARGE REQUIREMENTS

UNIT MUST BE IN SELF-TEST MODE

CANCEL 90-MINUTE TEST

30-SECOND TEST

90-MINUTE TEST

1 X PRESS AND RELEASE

PRESS AND HOLD

2 X PRESS AND RELEASE

A LOAD CALIBRATION CAN ALSO BE PERFORMED BY DISCONNECTING AND RECONNECTING THE UNIT CONNECTOR

ILB-CP-HE-SD MANUAL TESTING SEQUENCES

LOAD CALIBRATION

1

1

TOGGLE = SWITCHING TO ON STATE OR OFF STATE

2

WALL SWITCH TESTING IS NOT RECCOMMENDED FOR PHASE-DIMMING APPLICATIONS

3

UNIT CONNECTOR MUST BE CONNECTED

4

2

3

4

QUICK TEST

3 X PRESS AND RELEASE

4 X PRESS AND RELEASE

TBTS

TEST TYPE

WALL SWITCH

MINIMUM BATTERY CHARGE REQUIREMENTS

N/A

6 TOGGLES

8 TOGGLES

4 TOGGLES

N/A

2 HOURS

24 HOURS

24 HOURS

24 HOURS

ILB-CP-HE-SD MANUAL TESTING SEQUENCES  -  CANCELLING TEST

TBTS

TEST TYPE

WALL SWITCH

MINIMUM BATTERY CHARGE REQUIREMENTS

UNIT MUST BE IN SELF-TEST MODE

Manual Testing 

-  Manual Testing can be performed on the 

ILB-CP20-HE-SD-S

, provided the unit is fully charged, by 

pressing and releasing the 

TBTS 

or engaging the wall switch that controls the emergency luminaire.  Manual Testing 

cannot be initiated until the unit has received a full 24 hour charge. Manual Testing will not interfere with the automatic 

testing schedule of the 

ILB-CP20-HE-SD-S

 

and will display the same diagnosis indicators as automatic testing. Activate 

the desired test using the sequences in Table B below:

Table A: TBTS Self-Diagnostic codes          

Table B: Manual Test Sequences          

Table C: Cancel a Test

For more information on diagnosing 

ILB-CP20-HE-SD-S

 

failure codes, contact Customer Service. 

SERVICING SHOULD BE PERFORMED BY QUALIFIED PERSONNEL. 