INSTALLATION INSTRUCTIONS

CAUTION:   Before installing, make certain the A.C. power is off and the ILB-CP20-
HE-SD-S unit connector is disconnected.

1. FIXTURE 

 

The 

ILB-CP20-HE-SD-S

 can be used with most LED loads that operate at 20-60 VDC. 

 

1. The 

ILB-CP20-HE-SD-S

 series has been evaluated to and found compliant to UL standard 924. The as-installed  

   

    performance of system must meet or exceed all Federal, State, and Local code requirements.

 

2. Refer to Addendum 11042014 for detailed specifications and methods to calculate emergency light levels. 

2.  MOUNTING THE ILB-CP-HE

Mount the 

ILB-CP20-HE-SD-S

 

on or adjacent to the fixture in a position that does not interfere with the existing A.C. 

driver or any other hardware. Extend the flex conduit to the junction box or wireway channel and punch a 

7

/

8

 hole. Feed 

the wires and flex connector down through the hole in the fixture and secure in place with the flex connector nut. An 
optional T-bar mounting kit is available to mount the 

ILB-CP20-HE-SD-S

 

above the ceiling tile adjacent to the fixture. To 

order the optional T-bar mounting kit (part number TBMK) contact Customer Service.  

 
 When battery packs are remote mounted, the maximum distance between the unit and the LED Load must not  
 exceed 50 ft.

3. WIRING

    Refer to Illustration 3 for the appropriate wiring of the LED load and driver. Install in  

accordance with the National Electrical Code and local regulations. For additional wiring diagrams consult  

Customer Service. 

4.  INSTALLING THE THREADED BODY TEST SWITCH (TBTS)

  

Recessed Troffer Fixture

 – Select a convenient location with proper clearance in the ballast cover and drill or 

punch a 

7

/

8

 hole (

1

/

2

 knockout). Insert the 

7

/

8

 bushing into the hole. Push the plastic tube through the bushing. 

Route the leads of the 

TBTS

 through the plastic tube. Connect the LED wires from the unit to the 

TBTS

 (Red/

Black or Red w/tag to Red, White/Red to White). Push the entire assembly back into the tube until the lens collar 
rests against the plastic tube. The plastic tube should be adjusted so that the 

TBTS 

is within ¼

 of the fixture lens. 

The 

TBTS 

must be visible after installation. Refer to 

Illustration 1

.

  

Downlight Fixture

 – Select a convenient location on the fixture so the 

TBTS 

can be seen after installation. Allow 

for proper clearance inside the fixture and drill or punch a 

1

/

2

 hole. Remove the nut from the 

TBTS

. Push the 

TBTS

 housing into the 

1

/

2

 hole and secure with the nut. Connect the LED wires from the unit to the 

TBTS

 (Red/

Black or Red w/tag to Red, White/Red to White). Refer to 

Illustration 2

.

  

Note: 

The 

TBTS

 may be remote mounted up to a distance of 50 ft.  Additional mounting accessories may be  

required. Install in accordance with national and local safety codes, and only mount in locations and heights where 
the unit will not be subjected to tampering by unauthorized personnel.

 

Contact Customer Service for more details

7/8" BUSHING

PLASTIC TUBE

TBTS

CHANNEL

COVER

FLEX CONDUIT

FIXTURE LENS

Illustration 1  Recessed Troffer Fixture

Illustration 2  Downlight Fixture

ILB-CP20-HE-SD-S

OBSERVE PROPER POLARITY

FLEX 

CEILING

TILE

LED DRIVER AND ARRAY 

COMPARTMENT

TBTS

ILB-CP20-HE-SD-S