INSTALLATION INSTRUCTIONS
CAUTION: Before installing, make certain the A.C. power is off and the ILB-CP20-
HE-SD-A unit connector is disconnected.
1. FIXTURE
The
ILB-CP20-HE-SD-A
can be used with most LED loads that operate at 20-60 VDC.
1. The
ILB-CP20-HE-SD-A
series has been evaluated to and found compliant to UL standard 924. The as-installed
performance of system must meet or exceed all Federal, State, and Local code requirements.
2. Refer to Addendum 11042014 for detailed specifications and methods to calculate emergency light levels.
2. MOUNTING THE ILB-CP-HE
Mount the
ILB-CP20-HE-SD-A
on or adjacent to the fixture in a position that does not interfere with the existing A.C.
driver or any other hardware. Extend the flex conduit marked “A” to the junction box or wireway channel and punch a 7/8”
hole. Feed the wires and flex connector down through the hole in the fixture and secure in place with the flex connector
nut. An optional T-bar mounting kit is available to mount the
ILB-CP20-HE-SD-A
above the ceiling tile adjacent to the
fixture. To order the optional T-bar mounting kit (part number TBMK) contact Customer Service.
When battery packs are remote mounted, the maximum distance between the unit and the LED Load must not
exceed 50 ft.
3. WIRING
Refer to Illustration 3 for the appropriate wiring of the LED load and driver. Install in
accordance with the National Electrical Code and local regulations. For additional wiring diagrams consult
Customer Service.
4. INSTALLING THE THREADED BODY TEST SWITCH (TBTS)
For installation of the
TBTS
(Threaded Body Test Switch), cut a single gang switch box into the ceiling tile
adjacent to the fixture within reach of the
ILB-CP20-HE-SD-A
flex conduit marked “B”. After mounting the switch
box, connect flex to the box and route all leads inside the box. Refer to
Illustration 1
for typical mounting. For prop-
er operation, use only the accessory components provided with the unit
. See Page 1 of the Instruction Manual.
Note:
The
TBTS
may be remote mounted up to a distance of 50 ft. Additional mounting accessories may be
required. Install in accordance with national and local safety codes, and only mount in locations and heights where
the unit will not be subjected to tampering by unauthorized personnel.
Contact Customer Service for more details.
Illustration 1: Typical Installation (top view)
OPTIONAL T-BAR MOUNTING KIT
CEILING T-GRID
FIXTURE
FLEX “A” CONDUIT
FIXTURE
JUNCTION BOX
OR
WIRING
COMPARTMENT
SWITCH BOX FOR TBTS
(BOX NOT SUPPLIED)
FLEX “B” CONDUIT
TO TEST ACCESSORIES
ILB-CP20-HE-SD-A