IMPORTANT SAFEGUARDS

When using electrical equipment, basic safety precautions should always be followed, including the following:

READ AND FOLLOW ALL SAFETY INSTRUCTIONS

 1. 

WARNING 

– Risk of personal injury or property damage. When installing sealed lead-acid (SLA) batteries in 

sealed and gasketed luminaires a method of proper venting must be incorporated.

 2. 

CAUTION 

– This fixture provides more than one power supply output source. To reduce the risk of electrical 

shock, disconnect both normal and emergency sources by turning off the A.C. branch circuit and by discon-

necting the battery unit connector.

 3. 

CAUTION

 – Installation and servicing should be performed by 

qualified personnel only

. De-energize before 

opening.

 4.  Do not join the battery unit connector until installation is complete. If AC voltage is supplied to the unit with the 

unit connector open, the 

IPS

 Test Switch will start blinking after 10 seconds. This indicates that either the bat-

tery is disconnected or the unit connector is open.

 5.  The battery is field replaceable. Contact Customer Service for information on replacement. Use caution when 

replacing battery, and dispose of battery properly.

 6.  The 

ILB CP18 HE CW

 is for use with grounded LED luminaires listed to UL standards.  Not for use in heated 

air outlets or hazardous locations.

 7.  The 

ILB CP18 HE CW

 requires an unswitched A.C. power source of 120 to 277 volts AC, 50/60Hz.

 8. 

The 

ILB CP18 HE CW

 and A.C. driver 

must 

be on the same branch circuit.

  9.  Do not mount near gas or electric heaters.

 10.  The 

ILB CP18 HE CW

 should be mounted in locations and at heights where it will not readily be subjected to 

tampering by unauthorized personnel.

 11. The 

ILB CP18 HE CW

 will supply 20-58 VDC output at 18 Watts for 90 minutes.

12.   The 

ILB CP18 HE CW 

is certified in the CA Title 20 Modernized Appliance Efficiency Database System 

(MAEDBS) as a small battery charger.

 13.  Suitable for use in damp locations and enclosed and gasketed fixtures if proper ventilation method is present.
 14.  For use in -20° C minimum, 60° C maximum ambient temperatures.
 15.  The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition, void 

warranty, and result in non-compliance with UL specifications.

 16.  Do not use this equipment for other than intended use.

 17.  Install in accordance with the National Electrical Code and local regulations.

18.  Lighting fixture manufacturers, electricians, and end-users need to ensure product system compatibility before 

final installation.  See addendum for compatibility and covered luminaire requirements.

SAVE THESE  INSTRUCTIONS

ILB CP18 HE CW

COLD WEATHER

 

HIGH EFFICIENCY EMERGENCY

LIGHTING EQUIPMENT

FOR LED

INSTRUCTION MANUAL

P.O. BOX 11846  TUCSON, AZ 85734 

(520) 294-3292   •  FAX (520) 741-2837

www.iotaengineering.com

Patented. 

See iotaengineering.com/patents for more details

Pb

THIS UNIT CONTAINS
SEALED LEAD ACID BATTERIES

PLEASE RECYCLE OR DISPOSE OF PROPERLY

HIGH EFFICIENCY PERFORMANCE 
MEETS CA T20 BATTERY CHARGER 
EFFICIENCY STANDARDS

EMERGENCY LED DRIVER FOR USE 
WITH LED LUMINAIRES IDENTIFIED 
IN THE MANUFACTURER’S  
INSTALLATION INSTRUCTIONS

E99113