IOTA ILB-CP-HE-SD-XB Скачать руководство пользователя страница 3

Page 3

+ RED
LEAD

WHITE

LEAD

TBTS

7/8" BUSHING

CHANNEL COVER

PLASTIC TUBE (OPTIONAL)

TBTS

TBTS 

PUSH-IN CONNECTOR

CHANNEL COVER

TBTS

TBTS 

PUSH-IN CONNECTOR

EMERGENCY

DRIVER

EMERGENCY

DRIVER

Red

(LED)

White

(TBTS)

BLU/WHT

RED/WHT

WHT/RED

RED/BLK

Orange

(AC Input)

WHITE

ORG/BLK

UNSWITCHED AC LINE

SWITCHED AC LINE

NEUTRAL

BLACK

For proper operation, use only the accessory components provided with the unit

. See Page 1 of the Instruction Manual.  

Select 

a convenient location on the side of the fixture or channel compartment so that the 

TBTS

 can be seen after final installation. 

Allow for proper clearance and drill or punch a ½

 hole. Remove the nut from the 

TBTS

. Push the 

TBTS

 housing into the ½

 

hole and secure with the nut.

Attach the appropriate labels adjacent to the 

TBTS. 

Annotate Replacement Label with identical manufacturer 

part number(s). The Caution and the Replacement labels must be on the fixture in a readily visible location to 
anyone attempting to service the fixture.

Do not mate the ILB-CP-HE-SD-XB Unit Connector at this time.

When the installation is complete, switch the A.C. power on and join the 

ILB-CP-HE-SD-XB

 unit connector

Firmly insert the input power leads into the proper 
Orange Push-In Connector ports: Unswitched AC Line 
to ORG/BLK, Switched AC line to BLACK, and AC 
Neutral to WHITE. 

Push-in leads should be stripped to 9mm ± 0.5 mm.

The Push-In Connector is specified for single 

use. 

Removal of the leads after insertion can result 

in damage to the connector and product failure. For 

replacement push-in connectors, contact Customer 

Service.

The 

ILB-CP-HE-SD-XB

 and Normal AC Driver 

MUST 

be on 

the same branch circuit.

The 

ILB-CP-HE-SD-XB 

requires an 

unswitched

 A.C. power source of 120 to 277 VAC, 50/60Hz for maintaining the 

emergency battery in a state of readiness regardless of local switch position; therefore when used with switched fixtures, 
the 

ILB-CP-HE-SD-XB

 unswitched AC input must be wired ahead of the switch.

D

C.3

C.3

Firmly connect the TBTS wires into the proper inputs of the 

White Push-In Connector

 - The WHITE TBTS wire to the 

WHT/RED wire and the RED TBTS wire to the RED/BLK wire on White Push-In Connector.

C.2

STEP 4 - 

INSTALLING THE THREADED BODY TEST SWITCH (TBTS)

STEP 5 - 

WIRING THE AC INPUT

STEP 6 - 

FINISHING INSTALLATION

COMPLETING INSTALLATION

CAUTION: After the fixture is physically installed, make certain A.C. power is off and the unit connector is discon-

nected before completing the input wiring.

Table 1.1 -  Wire Gauge Guidelines       

LABELS -

Содержание ILB-CP-HE-SD-XB

Страница 1: ...nel 10 The ILB CP HE SD XB will supply 10 60VDC output at the individual rated specification for 90 minutes See individual units for output specifications 11 The ILB CP HE SD XB is certified in the CA Title 20 Modernized Appliance Efficiency Database System MAEDBS as a small battery charger 12 Suitable for use in damp locations and plenum spaces 13 Suitable for luminaires recessed Type IC intended...

Страница 2: ...B STEP 2 WIRING TO THE NORMAL LED DRIVER STEP 3 CONNECTING COMPONENTS TO THE PUSH IN PORT Mount the ILB CP SD XB in the driver lamp compartment or enclosed wireway so that the leads are not exposed providing at least space between normal AC driver and emergency driver components Install in accordance with National Electrical Code and local regulations Wire the ILB CP SD XB to the AC Driver input b...

Страница 3: ...irmly insert the input power leads into the proper Orange Push In Connector ports Unswitched AC Line to ORG BLK Switched AC line to BLACK and AC Neutral to WHITE Push in leads should be stripped to 9mm 0 5 mm The Push In Connector is specified for single use Removal of the leads after insertion can result in damage to the connector and product failure For replacement push in connectors contact Cus...

Страница 4: ...s its nominal input voltage will neces sitate a new Load Calibration see table below for how to conduct a manual Load Calibration Manual Testing can be performed on the ILB CP HE SD XB provided the unit is fully charged by pressing and releasing the TBTS or engaging the wall switch that controls the emergency luminaire Manual Testing cannot be initiated until the unit has received a full 24 hour c...

Отзывы: