IOTA ILB-CP-HE-SD-XB Скачать руководство пользователя страница 2

Page 2

Illustration 1: ILB-CP-HE-SD-XB Connections        

IOTA ILB-CP

EMERGENCY DRIVER

NORMAL AC DRIVER

Unit Connector

Push-In Ports
ORG: Input Power
WHT: TBTS
RED: LED Array

Normal Driver

Output

BLACK -

AC INPUT (120-277V)

WHITE - AC NEUTRAL

RED (+)

DRIVER LED OUTPUT

BLUE (-)

DRIVER LED OUTPUT

Normal Driver

Input

Red

(LED)

White

(TBTS)

BLU/WHT

RED/WHT

WHT/RED

RED/BLK

LED (-)

LED (+)

TBTS (WHITE)

TBTS (RED)

Orange

(AC Input)

WHITE

ORG/BLK

BLACK

INSTALLATION INSTRUCTIONS

CAUTION:   Before installing, make certain the A.C. power is off and the ILB-CP-HE-SD-XB 

unit connector is disconnected.

The 

ILB-CP-HE-SD-XB

 is designed for use with most LED loads that operate at 10-60 VDC. The ILB-CP-HE-SD-XB has been 

evaluated to and found compliant to UL 924 STANDARD FOR SAFETY Emergency Lighting and Power Equipment. The as-installed 
performance of system must meet or exceed all Federal, State, and Local code requirements.

 

STEP 1 - 

MOUNTING THE ILB-CP-HE-SD-XB

STEP 2 - 

WIRING TO THE NORMAL LED DRIVER

STEP 3 - 

CONNECTING COMPONENTS TO THE PUSH-IN-PORT

Mount the 

ILB-CP-SD-XB 

in the driver/lamp 

compartment or enclosed wireway so that the 
leads are not exposed, providing at least ½

″ 

space between normal AC driver and emergency 
driver components. Install in accordance with 
National Electrical Code and local regulations.

Wire the 

ILB-CP-SD-XB 

to the AC Driver input by connecting the BLACK wire to the Driver AC Input (120-277V), and the 

WHITE wire to the Driver AC Neutral.

Connect the LED array to the 

Red Push-In 

Connector. 

Observe proper polarity: NEG (-) lead 

to the BLU/WHT wire on Red Push-In Connector, 

POS (+) lead to the RED/WHT wire on Red Push-In 

Connector.

Push-in leads should be stripped to 9mm ± 0.5 mm.

Attention: The Push-In Connector is specified for single use. 

Removal of the leads after insertion can result in 

damage to the connector and product failure. For replacement push-in connectors, contact Customer Service.

Wire the 

ILB-CP-SD-XB 

to the AC Driver output by connecting the RED (+) wire to the Driver LED Output (+), and the 

BLUE (-) wire to the Driver LED Output (-).

A

C.1

C.1

C.2

B

Содержание ILB-CP-HE-SD-XB

Страница 1: ...nel 10 The ILB CP HE SD XB will supply 10 60VDC output at the individual rated specification for 90 minutes See individual units for output specifications 11 The ILB CP HE SD XB is certified in the CA Title 20 Modernized Appliance Efficiency Database System MAEDBS as a small battery charger 12 Suitable for use in damp locations and plenum spaces 13 Suitable for luminaires recessed Type IC intended...

Страница 2: ...B STEP 2 WIRING TO THE NORMAL LED DRIVER STEP 3 CONNECTING COMPONENTS TO THE PUSH IN PORT Mount the ILB CP SD XB in the driver lamp compartment or enclosed wireway so that the leads are not exposed providing at least space between normal AC driver and emergency driver components Install in accordance with National Electrical Code and local regulations Wire the ILB CP SD XB to the AC Driver input b...

Страница 3: ...irmly insert the input power leads into the proper Orange Push In Connector ports Unswitched AC Line to ORG BLK Switched AC line to BLACK and AC Neutral to WHITE Push in leads should be stripped to 9mm 0 5 mm The Push In Connector is specified for single use Removal of the leads after insertion can result in damage to the connector and product failure For replacement push in connectors contact Cus...

Страница 4: ...s its nominal input voltage will neces sitate a new Load Calibration see table below for how to conduct a manual Load Calibration Manual Testing can be performed on the ILB CP HE SD XB provided the unit is fully charged by pressing and releasing the TBTS or engaging the wall switch that controls the emergency luminaire Manual Testing cannot be initiated until the unit has received a full 24 hour c...

Отзывы: