114062B System Users Manual 

13 

 

 

C H A P T E R 6 

 

S

PECIFICATIONS

 

 

 

 

 

 

 

General Specifications

Input

Voltage  120 or 277Vac 1-phase 2-wire +10% -20%.  Contact factory for all other voltages.  

Input Power Walk-in  Walk-in limiting inrush current to less than 125%, 10 times for 1 line cycle

Input Frequency  60Hz, +/- 3%, 50Hz Available upon request

Synchronizing Slew Rate 1Hz per second nominal 

Protection  Input Circuit Breaker

Harmonic Distortion  < 10%

Power Factor  .5 lag/lead

Output

Voltage  120 or 277Vac 1-phase 2-wire.  Contact factory for all other voltages.

Static Voltage  Load current /-2%, battery dis/-12.5%

Dynamic Voltage  +/- 2% for +/-25% load step change, +/-3% for a 50% load step change, recovery within 3 cycles

Harmonic Distortion  < 3% THD for linear load

Overload  Fuse protected

Output Frequency  60Hz +/- .05Hz during emergency mode

Load Power Factor  .5 lag to .5 lead

Inverter Overload  115% for 10 minutes

Protection  Optional Distribution Circuit Breakers

Battery

Type  Valve-regulated sealed lead-calcium.  Contact factory for additional battery types.

Charger  Microprocessor controlled for various battery types and temperature compensating (recharge per UL924 spec)

Protection  Automatic low-battery disconnect; automatic restart upon utility return.

Disconnect  Fuse 

Optional Runtimes  Extended runtimes available.  Consult factory for additional information.

Environmental

Altitude  < 10,000 feet (above sea level) without derating

Operating Temperature  20 to 30 degree Celsius

Storage Temperature  -20 to 70 degrees Celsius (electronics only)

Relative Humidity  < 95% (non-condensing)

General

Design  Line interactive PWM inverter type utilizing IGBT technology with 2mS transfer time.

Generator Input  Compatible with generators. 

Control Panel  Microprocessor controlled 4 x 20-charactor vacuum fluorescent display with touch pad controls/functions & 

scrolling system status

Metering  Input & Output Voltage, Battery Voltage, Battery & Output Current, Output VA, Temperature, Inverter Wattage

Alarms  High/Low Battery Charger Fault, Near Low Battery, Low Battery, Load Reduction Fault, Output Overload,   

 High/Low AC Input Volts, High Ambient Temperature, Inverter Fault, Output Fault, Optional Circuit Breaker Trip 

Communications  RS-232 port (DB9).  Optional E-mail/fax modem.

Manual Maintenance Bypass  Optional Internal or optional external without internal distribution breakers.

Alarm Contacts   Optional Summary Form "C" Contacts

Warranty  1 year standard warranty includes all parts, labor, & travel expenses within 48 contiguous states.  Up to 10 years

 prorated warranty on batteries.  Extended warranties, preventative maintenance and customized service plans  

 are available.  

Factory Start-up  Purchase factory start-up & receive 1 additional year of warranty.

5 Year Service Plan  Purchase 5 year service plan & receive free factory start-up.

Physical

Cabinet  Freestanding NEMA Type 1

Cooling  Forced Air, during emergency mode.

Cable Entry  Top or Side

Access  Front 

Содержание IIS Series

Страница 1: ...IIS SERIES 1 5 kW 16 7 kW models with Fast Transfer Speed FT User s Manual...

Страница 2: ...CE OR INSTALLATION INFORMATION TELEPHONE 610 868 5400 24 HR HOTLINE FAX 610 954 8227 FOR YOUR PROTECTION PLEASE COMPLETE AND RETURN WARRANTY REGISTRATION CARD IMMEDIATELY This unit contains LETHAL VOL...

Страница 3: ...on battery type batteries contain either acid or alkali and can cause burns to skin and eyes If battery fluid is spilled on skin or in the eyes flush with fresh water and contact a physician immediat...

Страница 4: ...the inspection testing and maintenance of the emergency electrical power supply system shall be maintained in accordance with the Manufacturer s operating manual The log shall include The date on whi...

Страница 5: ...f the nominal DC voltage This feature protects the battery from being permanently damaged from a deep discharge that could cause cell reversal This battery protection feature is called Low Voltage Dis...

Страница 6: ...ice and Support FOR SERVICE or INSTALLATION INFORMATION TELEPHONE 610 868 5400 NOTE Please have your unit s Serial and Model numbers available when you call this number is located behind the right doo...

Страница 7: ...normal temperature of 25 C 77 F At about 45 C 113 F battery life is one fourth of normal Make sure that heaters sunlight air conditioners or outside air vents are not directed toward the batteries Th...

Страница 8: ...nverter chassis for approximately five seconds and then install the battery fuse If a large flash occurs the batteries are not connected properly Call service immediately 3 Energize the Mains AC input...

Страница 9: ...eptable level Black Out Brown Out or Transient the inverter will energize for at least one minute So if the power failure was a momentary glitch the LINE PRESENT would be illuminated but the inverter...

Страница 10: ...114062B System Users Manual 9...

Страница 11: ...Log Event Log Alarm Log User Setup Factory Setup Status System Information and Test Mode Once the desired menu has been reached press the ENTER key to gain access to this menu Once into the menu use...

Страница 12: ...nverter output Inverter Watts Indicates the DC Watts Battery Power the Inverter is processing Test Log To get to the Test log menu from the default screen press the ENTER key scroll to the Test log me...

Страница 13: ...screen press the ENTER key scroll to the User Setup menu using the left or right arrow key then press the ENTER key again The display will prompt for a password The password is left arrow right arrow...

Страница 14: ...ltage Near Low Battery 48VDC 43VDC 72VDC 65VDC 96VDC 86VDC 120VDC 108VDC 144VDC 130VDC 180VDC 162VDC 240VDC 216VDC Load Reduction Current Parameters are set in Amps AC Use the same technique as the ab...

Страница 15: ...Altitude 10 000 feet above sea level without derating Operating Temperature 20 to 30 degree Celsius Storage Temperature 20 to 70 degrees Celsius electronics only Relative Humidity 95 non condensing G...

Страница 16: ...ove Main Battery fuse CAUTION HAZARDOUS VOLTAGES STILL EXIST AT THE BATTERY TERMINAL BLOCK AND WITHIN THE SYSTEM AUTHORIZED SERVICE TECHNICIANS MUST DISCHARGE DC CAPACITORS BEFORE SERVICING EQUIPMENT...

Страница 17: ...lluminated and a slight hum should be heard from the inverter transformer The unit is now charging the batteries 6 Turn the Maintenance Bypass Switch handle from bypass mode BYPASS 2 O clock position...

Страница 18: ...r vents free of any obstruction If the environment tends to be extremely dusty occasionally blow away any accumulation of dust on components Please follow the shutdown procedure before cleaning CAUTIO...

Страница 19: ...xcessive transformer hum during normal run conditions 1 2 3 System draws excessive AC input current 1 2 3 Inverter will not run during a power failure 1 3 4 6 2 11 7 10 9 8 5 S Y M P T O M S Installat...

Страница 20: ...nt parts and labor rates A minimum rate will be assessed The manufacturer will not proceed with repairs of an out of warranty unit until authorization in the form of a purchase order is received from...

Отзывы: