114062B System Users Manual 

11 

 

 

Meter Functions

 

To get to the meter functions from the default screen, press the 

ENTER

 key, scroll to 

the METER menu using the left or the right arrow key, then press the 

ENTER

 key 

again.  Use left or the right arrow key to view the meter function desired. 

Table 5.2 Meter Functions 

Function 

Description 

Voltage Input  Measures the AC Input Voltage to the Inverter. 

Voltage Output  Measures the AC Output Voltage from the Inverter. 

Current Output  Measures the AC Output Current from the Inverter. If there are Normally Off 

loads connected, it will read the sum of Normally On and Normally Off 

outputs. 

Battery Voltage  Measures DC Battery Voltage. 

Battery Current  Measures the DC Battery Current. When in charge mode, the current will be 

positive. When in Inverter mode, the current will be negative. 

Battery 

Temperature 

Optional feature – measures temperature at the battery. 

Internal 

Temperature 

Measures the ambient temperature inside the system. 

Inverter Minutes  Indicates the total minutes the system has run on inverter. 

System Days  Indicates the total days the system has been on-line. 

VA Output 

Indicates the AC Volts-Amps of the Inverter output. 

Inverter Watts  Indicates the DC Watts (Battery Power) the Inverter is processing. 

 

Test Log 

 

To get to the Test log menu from the default screen, press the 

ENTER

 key, scroll to 

the Test log menu using the left or right arrow key, then press the 

ENTER

 key again.  

Use the left or right arrow key to view the test desired, and the press the 

ENTER

 key 

for more information. 
The Test log indicates the Date, Time and Duration of the test.  It also indicates if it 

was a monthly or yearly test, and it records the output voltage, the output current, the 

ambient temperature, and if there were any alarm conditions. 
The numbers of tests that can be captured in the test log are 75.  The format is first 

in is first out so; test number one is the most recent test. 
 

Event Log 

 
To get to the Event log menu from the default screen, press the 

ENTER

 key, scroll to 

the Event log menu using the left or right arrow key, then press the 

ENTER

 key 

again.  Use the left or right arrow key to view the event desired, and then press the 

ENTER

 key for more information. 

The Event log is identical to the test log in parameters it stores.  The Event log 

captures data every time there is a transfer from utility power to battery power.  The 

numbers of events that can be captured in the event log are 75.  The format is first in 

is first out so; event number one is the most recent event. 

 

Содержание IIS Series

Страница 1: ...IIS SERIES 1 5 kW 16 7 kW models with Fast Transfer Speed FT User s Manual...

Страница 2: ...CE OR INSTALLATION INFORMATION TELEPHONE 610 868 5400 24 HR HOTLINE FAX 610 954 8227 FOR YOUR PROTECTION PLEASE COMPLETE AND RETURN WARRANTY REGISTRATION CARD IMMEDIATELY This unit contains LETHAL VOL...

Страница 3: ...on battery type batteries contain either acid or alkali and can cause burns to skin and eyes If battery fluid is spilled on skin or in the eyes flush with fresh water and contact a physician immediat...

Страница 4: ...the inspection testing and maintenance of the emergency electrical power supply system shall be maintained in accordance with the Manufacturer s operating manual The log shall include The date on whi...

Страница 5: ...f the nominal DC voltage This feature protects the battery from being permanently damaged from a deep discharge that could cause cell reversal This battery protection feature is called Low Voltage Dis...

Страница 6: ...ice and Support FOR SERVICE or INSTALLATION INFORMATION TELEPHONE 610 868 5400 NOTE Please have your unit s Serial and Model numbers available when you call this number is located behind the right doo...

Страница 7: ...normal temperature of 25 C 77 F At about 45 C 113 F battery life is one fourth of normal Make sure that heaters sunlight air conditioners or outside air vents are not directed toward the batteries Th...

Страница 8: ...nverter chassis for approximately five seconds and then install the battery fuse If a large flash occurs the batteries are not connected properly Call service immediately 3 Energize the Mains AC input...

Страница 9: ...eptable level Black Out Brown Out or Transient the inverter will energize for at least one minute So if the power failure was a momentary glitch the LINE PRESENT would be illuminated but the inverter...

Страница 10: ...114062B System Users Manual 9...

Страница 11: ...Log Event Log Alarm Log User Setup Factory Setup Status System Information and Test Mode Once the desired menu has been reached press the ENTER key to gain access to this menu Once into the menu use...

Страница 12: ...nverter output Inverter Watts Indicates the DC Watts Battery Power the Inverter is processing Test Log To get to the Test log menu from the default screen press the ENTER key scroll to the Test log me...

Страница 13: ...screen press the ENTER key scroll to the User Setup menu using the left or right arrow key then press the ENTER key again The display will prompt for a password The password is left arrow right arrow...

Страница 14: ...ltage Near Low Battery 48VDC 43VDC 72VDC 65VDC 96VDC 86VDC 120VDC 108VDC 144VDC 130VDC 180VDC 162VDC 240VDC 216VDC Load Reduction Current Parameters are set in Amps AC Use the same technique as the ab...

Страница 15: ...Altitude 10 000 feet above sea level without derating Operating Temperature 20 to 30 degree Celsius Storage Temperature 20 to 70 degrees Celsius electronics only Relative Humidity 95 non condensing G...

Страница 16: ...ove Main Battery fuse CAUTION HAZARDOUS VOLTAGES STILL EXIST AT THE BATTERY TERMINAL BLOCK AND WITHIN THE SYSTEM AUTHORIZED SERVICE TECHNICIANS MUST DISCHARGE DC CAPACITORS BEFORE SERVICING EQUIPMENT...

Страница 17: ...lluminated and a slight hum should be heard from the inverter transformer The unit is now charging the batteries 6 Turn the Maintenance Bypass Switch handle from bypass mode BYPASS 2 O clock position...

Страница 18: ...r vents free of any obstruction If the environment tends to be extremely dusty occasionally blow away any accumulation of dust on components Please follow the shutdown procedure before cleaning CAUTIO...

Страница 19: ...xcessive transformer hum during normal run conditions 1 2 3 System draws excessive AC input current 1 2 3 Inverter will not run during a power failure 1 3 4 6 2 11 7 10 9 8 5 S Y M P T O M S Installat...

Страница 20: ...nt parts and labor rates A minimum rate will be assessed The manufacturer will not proceed with repairs of an out of warranty unit until authorization in the form of a purchase order is received from...

Отзывы: