1. CONNECTING THE BATTERY CHARGER INPUT (FIGURE 1)

Battery Charger Input leads serve as your normal power sense and charging input for the battery. They require 

unswitched

 AC 

input of 120 or 277 VAC. If a local switch is present on the designated emergency circuit, the battery charger input leads must 

be wired ahead of the switch.

A.

 For 120V

 supply, connect the AC line wire to the BLACK Battery Charger Input lead. 

For 277V

 supply, connect the AC 

line wire to the ORANGE Battery Charger Input lead.  

CAUTION: Cap the unused BLACK or ORANGE input wire. Failure 

to do so may result in equipment failure and void the warranty.

B. Connect the Neutral wire to the WHITE Battery Charger Input lead.
C. Connect the ground wire in accordance with local and national codes. A GREEN wire is provided for this purpose.

2. CONNECTING THE NORMAL AC INPUT (FIGURE 1)

Normal AC Input leads allow for your fixture(s) to operate in normal power situations while maintaining emergency 

capabilities.  Before connecting the Normal AC Input leads, see 

Figure 1

 to determine which normal power situation best 

fits your application.  In all applications:

A. 

For 120V 

supply, connect AC line input to the BLACK Normal AC Input lead.  

For 277V 

supply, connect the AC line 

input to the ORANGE Normal AC Input lead.  

Cap the unused lead.

B. Connect the AC line Neutral to the WHITE Normal AC Input lead. 

3. CONNECTING EMERGENCY FIXTURES (FIGURE 1)

A. Connect emergency fixtures to the output leads YELLOW/VIOLET for 120/277V and GRAY for NEUTRAL. All remote 

circuitry is to be wired in accordance with Article 700 of the National Electric Code. Do not exceed the total rating of the  

IIS 550 I

When making connections to the IIS 550 I, DO NOT connect the Input Neutral (WHITE) to the Output 

Neutral (GRAY).

B Connect the Fixture Supply Ground to the 

IIS 550 I

 Ground. 

Consult the 

IIS 550 I

 

Application Notes

 for connecting the unit to specific lighting loads. Application Notes are available on the 

internet or through Customer Service.

COMPONENT HOUSING / CIRCUITRY

(CAUTION: DO NOT OPEN)

BATTERY

4

INTERNAL CIRCUIT BREAKER

(SELECT PROPER VOLTAGE LEAD)
VIOLET - 120 VAC, YELLOW - 277 VAC

5

BATTERY CONNECTION

TEST SWITCH

LED INDICATORS

GROUND WIRE

INPUT, OUTPUT, AND 
BATTERY CHARGER LEADS

FIGURE 2 - 

IIS 550 I  SIDE

4. CONNECTING THE INTERNAL CIRCUIT BREAKER (FIGURE 2)

A. Select the proper voltage lead (VIOLET for 120VAC or YELLOW for 277VAC) and connect it to the circuit breaker.  

Cap the unused lead. Push the circuit breaker switch to the ‘closed’ position so that the indicator on the circuit breaker 

shows RED. 

      CAUTION: Before proceeding to Wiring Step 5, make sure that all unused wires are properly capped.  

      Failure to do so may result in an unsafe condition and equipment failure.

5. INSTALLING THE BATTERY (FIGURE 2)
 

 ATTENTION: 

Use only battery part number 

IIS 550 I BAT

 with the unit. 

See Page 1 of this instruction manual

.

  

A. Before installing the battery, check the torque on the hardware that connects the polarized connector to the  

 

terminals as these connections may have loosened in transit and storage. 
 

Battery Torque Ratings:

 initial torque is 65 in/lbs, annual is 52 in/lbs.

    B. Install the battery into the 

IIS 550 I

 with the terminal posts facing toward the front of the unit. NOTE: The 

 

  IIS 550 I

 battery is heavy. To avoid injury, exercise caution when handling the battery.

    C. Plug the battery connector together.

Note: Neither the indicator lights nor the emergency fixtures will illuminate at this time.

 Also, please note that there are 

2 battery tie down lugs in the event that it is required that the battery be held in place. Please contact IOTA Engineering  
Customer Service to purchase this accessory if needed.

Содержание IIS 550 I

Страница 1: ...for use with HID lighting 8 Use only the battery part number specified for use with the IIS 550 I Failure to do so may cause an unsafe condition will void warranty and result in non compliance with UL specifications 9 The IIS 550 I uses a sealed valve regulated lead acid battery Batteries can be punctured if not handled properly therefore use caution when servicing batteries In the event battery a...

Страница 2: ...ONS IIS_375_550_normally on EPS INVERTER ALWAYS ON FIXTURE WHITE BLK 120V ORG 277V COMMON 120 277 V WHITE GREEN GROUND GRAY YEL VIO NEUTRAL 120 277V CIRCUIT MUST BE ISOLATED FROM NORMAL CIRCUITS BLK 120V ORG 277V 1 NORMAL AC INPUT UNSWITCHED OUTPUT BATTERY CHARGER INPUT UNSWITCHED CIRCUIT BREAKER VIOLET 120V YELLOW 277V 4 IIS INVERTER 2 3 IIS_375_550_normally on EPS INVERTER SWITCHED FIXTURE 1 NOR...

Страница 3: ...WHITE to the Output Neutral GRAY B Connect the Fixture Supply Ground to the IIS 550 I Ground Consult the IIS 550 I Application Notes for connecting the unit to specific lighting loads Application Notes are available on the internet or through Customer Service COMPONENT HOUSING CIRCUITRY CAUTION DO NOT OPEN BATTERY 4 INTERNAL CIRCUIT BREAKER SELECT PROPER VOLTAGE LEAD VIOLET 120 VAC YELLOW 277 VAC ...

Страница 4: ...st Switch The Ready Yellow Indicator will come on Normally Off emergency fixtures will extinguish The equipment is supplied with an automatic solid state charger designed to fully recharge the battery within 72 hours after AC power is restored and then maintain the battery in a fully charged state Allow the battery to charge for a minimum of 72 hours after installation or power failure before cond...

Отзывы: