Wiring

INSTALLATION INSTRUCTIONS

CAUTION:   Before installing, make certain the A.C. power is off.

NOTE:

 The battery is shipped in separate packaging for ease of handling. Store the battery in a cool, dry and safe  

location until ready for installation. The battery may be kept in storage for up to 3 months without recharging.

CAUTION: 

This is a dual input and output voltage unit. It can be connected to either a 120 or 277 volt supply. 

 

The input and output voltages must match

.

Mounting the IIS 550 I

1) Remove the front cover of the 

IIS 550 I 

by removing the two (2) screws located at the top of cover.

2) Knock out the keyhole slots at the rear of the unit and use for mounting the

 IIS 550 I

 securely to the wall. There is an additional 

round hole for a #10 screw in the cabinet. Code requires that an additional screw be used through this hole to prevent the unit 
from being inadvertently lifted up off the keyhole slots. 

Do not drill any holes in this unit

.

 

3)

 

Extend an unswitched AC supply, normally-on lamp supply (if used), and the load wires to the unit. 1/2

 conduit knockouts 

are provided in the back and sides of the unit for wires to pass through. NOTE: Input and output wires must be run in separate 
conduits. 

CAUTION

: Do not drill holes into the cabinet; drill filings may damage the unit and keep it from operating.

CAUTION: The IIS 550 I must be mounted securely. Do not rely on the junction box for supporting the weight of the 

unit. Mount the IIS 550 I securely to the wall using the keyhole slots provided. 

ALWAYS CONSULT LOCAL CODES FOR STRUCTURAL REQUIREMENTS WHEN MOUNTING THE UNIT.

FIGURE 1 - 

IIS 550 I  WIRING CONNECTIONS

IIS_375_550_normally-on.EPS

INVERTER - ALWAYS ON FIXTURE

WHITE

BLK (120V)

ORG (277V)

COMMON

120 / 277 V

WHITE

GREEN

GROUND

GRAY

YEL/VIO

NEUTRAL

120/277V

CIRCUIT MUST BE 
ISOLATED FROM 
NORMAL CIRCUITS.

BLK (120V)

ORG (277V)

1

NORMAL AC

INPUT

(UNSWITCHED)

OUTPUT

BATTERY CHARGER

INPUT (UNSWITCHED)

CIRCUIT 

BREAKER

VIOLET (120V)

YELLOW (277V)

4

IIS INVERTER

2

3

IIS_375_550_normally-on.EPS

INVERTER - SWITCHED FIXTURE

1

NORMAL AC

INPUT (SWITCHED)

OUTPUT

BATTERY CHARGER

INPUT (UNSWITCHED)

CIRCUIT 

BREAKER

VIOLET (120V)

YELLOW (277V)

WHITE

BLK (120V)

ORG (277V)

COMMON

120 / 277 V

WHITE

GREEN

GROUND

GRAY

YEL/VIO

NEUTRAL

120/277V

CIRCUIT MUST BE 
ISOLATED FROM 
NORMAL CIRCUITS.

BLK (120V)

ORG (277V)

WALL SWITCH

4

IIS INVERTER

2

3

ALTERNATE 
AC INPUT 
(IF PRESENT)

IIS_375_550_normally-on.EPS

INVERTER - NORMALLY OFF FIXTURE (EMERGENCY MODE ONLY)

1

NORMAL AC

INPUT

OUTPUT

BATTERY CHARGER

INPUT (UNSWITCHED)

CIRCUIT 

BREAKER

VIOLET (120V)

YELLOW (277V)

CIRCUIT MUST BE 
ISOLATED FROM 
NORMAL CIRCUITS.

4

IIS INVERTER

2

3

WHITE

BLK (120V)

ORG (277V)

COMMON

120 / 277 V

WHITE

GREEN

GROUND

GRAY

YEL/VIO

NEUTRAL

120/277V

BLK (120V)

ORG (277V)

CAP UNUSED

LEADS

- ALWAYS ON FIXTURES

Fixtures are used for both normal and 
emergency power conditions.  During 
a loss of normal AC power, the IIS 
automatically senses the drop in line 
voltage, and powers the fixtures with its 
internal battery.  

- SWITCHED FIXTURES

Fixtures are used for both normal and 
emergency power conditions, and are 
controlled by a local switching device.  
During a loss of normal AC power, the 
IIS automatically senses the drop in line 
voltage, and powers the fixtures with 
its internal battery, regardless of the 
position of the switching device.  

- NORMALLY OFF FIXTURES

Fixtures on the emergency circuit are 
used in emergency mode only, and 
are not energized during normal power 
conditions (Note: Normal AC Input leads 
are not connected). 

Содержание IIS 550 I

Страница 1: ...for use with HID lighting 8 Use only the battery part number specified for use with the IIS 550 I Failure to do so may cause an unsafe condition will void warranty and result in non compliance with UL specifications 9 The IIS 550 I uses a sealed valve regulated lead acid battery Batteries can be punctured if not handled properly therefore use caution when servicing batteries In the event battery a...

Страница 2: ...ONS IIS_375_550_normally on EPS INVERTER ALWAYS ON FIXTURE WHITE BLK 120V ORG 277V COMMON 120 277 V WHITE GREEN GROUND GRAY YEL VIO NEUTRAL 120 277V CIRCUIT MUST BE ISOLATED FROM NORMAL CIRCUITS BLK 120V ORG 277V 1 NORMAL AC INPUT UNSWITCHED OUTPUT BATTERY CHARGER INPUT UNSWITCHED CIRCUIT BREAKER VIOLET 120V YELLOW 277V 4 IIS INVERTER 2 3 IIS_375_550_normally on EPS INVERTER SWITCHED FIXTURE 1 NOR...

Страница 3: ...WHITE to the Output Neutral GRAY B Connect the Fixture Supply Ground to the IIS 550 I Ground Consult the IIS 550 I Application Notes for connecting the unit to specific lighting loads Application Notes are available on the internet or through Customer Service COMPONENT HOUSING CIRCUITRY CAUTION DO NOT OPEN BATTERY 4 INTERNAL CIRCUIT BREAKER SELECT PROPER VOLTAGE LEAD VIOLET 120 VAC YELLOW 277 VAC ...

Страница 4: ...st Switch The Ready Yellow Indicator will come on Normally Off emergency fixtures will extinguish The equipment is supplied with an automatic solid state charger designed to fully recharge the battery within 72 hours after AC power is restored and then maintain the battery in a fully charged state Allow the battery to charge for a minimum of 72 hours after installation or power failure before cond...