Page 4
TYPICAL WIRING DIAGRAM
For wiring diagrams of ballast/drivers not shown, consult our Customer Service.
68016-103
REV 1800
TYPICAL GENERATOR APPLICATION WITH 0-10V DIMMING CONTROL
ETS_DR_SEPARATELY-DERIVED
REV 071718
YELLO
W
YELLO
W/WHITE
ETS-DR
EMERGENCY
CONTROL DEVICE
RED LED
NORMAL POWER INDICATOR
(OPTIONAL)
EMERGENCY
POWER
EMERGENCY
PANEL
RED (EMERGENCY LINE)
WHITE (NEUTRAL SENSE)
BLUE (SWITCH SENSE)
BLACK (NORMAL POWER SENSE)
G
NORMAL
PANEL
DOUBLE POLE UL
1008 TRANSFER SWITCH
WALL SWITCH OR OTHER
ON-OFF DEVICE (IF PRESENT)
NORMAL
POWER
N
NEUTRAL
BLK/ORG
VIOLET
VIOLET
VIOLET
RED/WHT (EMERGENCY COMMON)
120-277V
GRAY
NEUTRAL
HOT
HOT
HOT
NEUTRAL
NEUTRAL
NEUTRAL
HOT
0-10 V DIMMING
CONTROL
AC DRIVER / BALLAST
TYPICAL GENERATOR APPLICATION WITH 0-10V DIMMING CONTROL
ETS_DR
REV 071718
YELLO
W
YELLO
W/WHITE
ETS-DR
EMERGENCY
CONTROL DEVICE
RED LED
NORMAL POWER INDICATOR
(OPTIONAL)
EMERGENCY
POWER
EMERGENCY
PANEL
RED (EMERGENCY LINE)
WHITE (NEUTRAL SENSE)
BLUE (SWITCH SENSE)
BLACK (NORMAL POWER SENSE)
G
NORMAL
PANEL
SINGLE POLE UL 1008
TRANSFER SWITCH
NEUTRAL BUS FOR
EMERGENCY PANEL
WALL SWITCH OR OTHER
ON-OFF DEVICE (IF PRESENT)
NORMAL
POWER
N
BLK/ORG
VIOLET
VIOLET
VIOLET
RED/WHT (EMERGENCY COMMON)
120-277V
GRAY
NEUTRAL
HOT
HOT
HOT
NEUTRAL
NEUTRAL
HOT
0-10 V DIMMING
CONTROL
AC DRIVER / BALLAST
NEUTRAL BUS FOR
NORMAL PANEL
TYPICAL CIRCUIT DIAGRAM - SEPARATELY DERIVED SYSTEM (SWITCHED NEUTRAL)
TYPICAL CIRCUIT DIAGRAM 2 - NON SEPARATELY DERIVED SYSTEM