background image

Page 4

TYPICAL WIRING DIAGRAM

For wiring diagrams of ballast/drivers not shown, consult our Customer Service.

68016-103
REV 1800

TYPICAL GENERATOR APPLICATION WITH 0-10V DIMMING CONTROL

ETS_DR_SEPARATELY-DERIVED

REV 071718

YELLO

W

YELLO

W/WHITE

ETS-DR

 EMERGENCY

CONTROL DEVICE

RED LED

NORMAL POWER INDICATOR

(OPTIONAL)

EMERGENCY

POWER

EMERGENCY

PANEL

RED  (EMERGENCY LINE)

WHITE (NEUTRAL SENSE)

BLUE (SWITCH SENSE)

BLACK (NORMAL POWER SENSE)

G

NORMAL

PANEL

DOUBLE POLE UL

1008 TRANSFER SWITCH

WALL SWITCH OR OTHER

ON-OFF DEVICE (IF PRESENT)

NORMAL

POWER

N

NEUTRAL

BLK/ORG

VIOLET

VIOLET

VIOLET

RED/WHT (EMERGENCY COMMON)

120-277V

GRAY

NEUTRAL

HOT
HOT

HOT

NEUTRAL

NEUTRAL

NEUTRAL

HOT

0-10 V DIMMING

CONTROL

AC DRIVER / BALLAST

TYPICAL GENERATOR APPLICATION WITH 0-10V DIMMING CONTROL

ETS_DR

REV 071718

YELLO

W

YELLO

W/WHITE

ETS-DR

 EMERGENCY

CONTROL DEVICE

RED LED

NORMAL POWER INDICATOR

(OPTIONAL)

EMERGENCY

POWER

EMERGENCY

PANEL

RED  (EMERGENCY LINE)

WHITE (NEUTRAL SENSE)

BLUE (SWITCH SENSE)

BLACK (NORMAL POWER SENSE)

G

NORMAL

PANEL

SINGLE POLE UL 1008 

TRANSFER SWITCH

NEUTRAL BUS FOR

EMERGENCY PANEL

WALL SWITCH OR OTHER

ON-OFF DEVICE (IF PRESENT)

NORMAL

POWER

N

BLK/ORG

VIOLET

VIOLET

VIOLET

RED/WHT (EMERGENCY COMMON)

120-277V

GRAY

NEUTRAL

HOT
HOT

HOT

NEUTRAL

NEUTRAL

HOT

0-10 V DIMMING

CONTROL

AC DRIVER / BALLAST

NEUTRAL BUS FOR

NORMAL PANEL

TYPICAL CIRCUIT DIAGRAM - SEPARATELY DERIVED SYSTEM (SWITCHED NEUTRAL)

TYPICAL CIRCUIT DIAGRAM 2 - NON SEPARATELY DERIVED SYSTEM

Отзывы: