INSTALLATION INSTRUCTIONS

CAUTION:   Before installing, make certain the AC power is off.

1.  MOUNTING THE ETS-DR

Integral (No Flex)

 – Remove the driver channel cover. Mount the 

ETS-DR

 in the ballast/driver channel 

at least ½

 away from the AC driver(s).

Flex (ETS-DR-A)

 – Mount the 

ETS-DR-A 

on or adjacent to the fixture in a position that does not interfere 

with the existing AC ballast/driver or any other hardware. Extend the flex conduit to the junction box or 

wireway channel and punch a 

7

/8

 hole. Feed the wires and flex connector down through the hole in the 

fixture and secure in place with the flex connector nut. 

2. WIRING

  

Refer to the wiring diagram on the back page for the appropriate wiring of the 

ETS-DR

. Install in ac-

cordance with the National Electrical Code and local regulations. For additional wiring diagrams consult 

Customer Service.

3.  INSTALLING THE AC INDICATOR

   

Integral (No Flex)

 – Select a convenient location with proper clearance in the ballast/driver channel 

cover and drill or punch a 

7

/

8

 hole (

1

/

2

 knockout). Insert the 

7

/

8

 bushing into the hole. Push the plastic 

tube through the bushing. Disconnect the leads from the 

AC Indicator

 housing and route the leads 

down the plastic tube. Reconnect the leads to the housing, observing the proper polarity (Yellow lead 

to red marked or positive (+) red tab). Push the entire assembly back into the tube until the lens collar 

rests against the plastic tube. The plastic tube should be adjusted so that the 

AC Indicator 

is within 

¼

″ 

of the fixture lens. The 

AC Indicator

 must be visible after installation. Refer to

 Illustration 1 

for an 

example of integral mounting in a recessed troffer fixture.

   

Flex (ETS-DR-A)

 – Select a convenient location on the fixture so the 

AC Indicator

 can be seen after 

installation. Allow for proper clearance inside the fixture and drill or punch a ½

″ 

hole. Disconnect the 

leads from the 

AC Indicator 

housing. Push the 

AC Indicator

 housing into the ½

″ 

hole until it is firmly 

locked in place. Reconnect the leads, observing the proper polarity (Yellow lead to red marked or posi-

tive (+) red tab). Refer to

 Illustration 2 

for an example of mounting on a downlight fixture.

7/8" BUSHING

FIXTURE

BALLAST CHANNEL COVER

PLASTIC TUBE

CHARGE INDICATOR
LIGHT

FIXTURE LENS

Illustration 1: Integral (No Flex) Mounting

Recessed Troffer Fixture

ETS-DR

Illustration 2: Flex (ETS-DR-A) Mounting

Downlight Fixture

OBSERVE PROPER POLARITY

FLEX 

CEILING

TILE

LED DRIVER AND ARRAY 

COMPARTMENT

TBTS

ETS-DR-A

CHARGE INDICATOR
LIGHT

AC DRIVER/BALLAST
COMPARTMENT

Отзывы: