SEH50-SEH100-SEH200

Heavy Duty High Head Sewage Pumps

OPERATION MANUAL

Dated: 03/22/2018

Document Name: SEH50-SEH100-SEH200_OM

Page 6 of 12

www.ionproducts.net

Submergence

The pump should always be operated in the 

submerged condition. The minimum sump liquid level 

should never be less than above the pump’s motor, 

unless very briefly.

Discharge Piping

Install discharge piping or hose assembly to the pump. 

Discharge piping should be as short as possible and 

sized  no  smaller  than  the  pump  discharge.  Do  not 

reduce  the  discharge  pipe  size  below  that  which  is 

provided on the pump. Both a check valve and a shut-

off valve are recommended for each pump. The check 

valve is used to prevent backflow into the sump. The 

shut-off  valve  is  used  to  manually  stop  system  flow 

during pump servicing. Be sure the discharge pipe 

has a 1/8” diameter hole approx. 5” from end nearest 

volute and oriented towards the pump body.

Control Panel

Single phase series sewage pumps DO NOT require 

a control panel, but do require a level control.

Motor

Each motor is provided with heat sensor thermostats 

attached directly to the motor windings. The 

thermostats open if the motor windings see excessive 

heat  and,  in  turn,  open  the  motor  contactor  in  the 

control  panel  when  used,  breaking  the  power  to 

the pump. When the motor is stopped due to an 

overheated condition, it will not start until the motor 

has cooled.

Pre-Operation

Check Voltage And Phase

Before  operating  pump,  check  to  make  sure  that 

voltage and phase information stamped on the pump’s 

identification plate matches the available power.

Check Pump Rotation

Before  putting  pump  into  service  for  the  first  time, 

the motor rotation must be checked. Improper motor 

rotation can result in poor pump performance and can 

damage the motor and/or pump.

Identification Plate

Note the numbers on the pumps identification plate 

and record in this manual for future reference.

CAUTION: Electrical Connections

Turn circuit breaker off before plugging or unplugging 

the switch and/or pump.

It is recommended that the level control float should 

be set to insure that the liquid in the sump never 

drops below the top of the motor housing. The level 

control should have adequate clearance so it cannot 

hang up in it’s swing and that the pump is completely 

submerged  when  the  level  control  is  in  the  “Off  ” 

mode. Minimum tether length is 3.50”. 

By adjusting the cord tether the control level can be 

changed. DO NOT USE THE POWER CABLE TO 

LIFT PUMP.

Pump-Down Test

Be  sure  pump  has  been  plugged  in, 

lowered into 

the basin or sump, check the system by filling  with 

liquid and allowing the pump to operate  through its 

pumping cycle. The time needed to empty the system, 

or pump-down time along with the volume of water, 

should be recorded.

Thermal Protection

The normally closed (N/C) over temperature sensor 

is embedded in the motor windings and will detect 

excessive heat in the event an overload condition 

occurs.

The thermal sensor will trip when the windings 

become too hot and will automatically reset when the 

pump motor cools to a safe temperature. 

In  the  event  of  an  over  temperature,  the  source  of 

this condition should be determined and repaired 

immediately. Thermal protection shall not be used as a 

motor overload device.

Maintenance

Minimal maintenance is required. Perform the 

following checks when pump is removed from 

operation or when pump performance deteriorates:

1.  Inspect motor chambers for oil level and 

contamination.

2.  Inspect impeller and body for excessive build-

up or clogging.

3.  Inspect motor and bearings.

4.  Inspect seal for wear or leakage.

Содержание SEH100M-03

Страница 1: ...he operator that the failure to follow an instruction may damage the pump and or the system Safety Warnings CAUTION Read these safety warnings first before installing servicing or operating any pump B...

Страница 2: ...NING Installation wiring and junction connections must be in accordance with the National Electric Code and all applicable state and local codes Requirements may vary depending on usage and location W...

Страница 3: ...quently Never handle connected power cords with wet hands Never let cords or plugs lie in water outside the pit These pumps are offered in a three phase and single phase wiring configuration Voltages...

Страница 4: ...odel HP Volt Ph Nema Start Code FLA Cord Size Cord Type Cord O D Inches SEH50M 11 0 5 60 115 1 3450 12 0 SOW 16 3 0 43 SEH50M 21 0 5 60 230 1 3450 6 0 SOW 16 3 0 43 SEH50M 03 0 5 60 208 3 3450 4 2 SOW...

Страница 5: ...s and connected to discharge pipe so that space is provided under pump for entrance of sewage Pump inlet should not be closer than 2 inches from bottom of sump It is not generally desirable to install...

Страница 6: ...per motor rotation can result in poor pump performance and can damage the motor and or pump Identification Plate Note the numbers on the pumps identification plate and record in this manual for future...

Страница 7: ...ags or labels have been removed 5 Used in a heavy grease application 6 Used in applications exceeding the designed temperature range of 32 104 degrees F Troubleshooting Pump does not run and or just h...

Страница 8: ...5010 2 BEARING 10 091EP5011 1 C RING 11 091EP7512 1 ROTOR ASSY 1 2 HP 091EP1012 1 ROTOR ASSY 1 0 HP 091SWH212 1 ROTOR ASSY 2 0 HP 12 091EP5013 1 SPRING WASHER 13 091EP5014 1 TOP COVER 14 091EP5015 1 G...

Страница 9: ...High Head Sewage Pumps OPERATION MANUAL Dated 03 22 2018 Document Name SEH50 SEH100 SEH200_OM Page 9 of 12 www ionproducts net Exploded View 1 2 3 4 5 7 8 9 11 13 16 17 18 5 19 20 21 22 23 14 15 25 26...

Страница 10: ...SEH50 SEH100 SEH200 Heavy Duty High Head Sewage Pumps OPERATION MANUAL Dated 03 22 2018 Document Name SEH50 SEH100 SEH200_OM Page 10 of 12 www ionproducts net Notes...

Страница 11: ...SEH50 SEH100 SEH200 Heavy Duty High Head Sewage Pumps OPERATION MANUAL Dated 03 22 2018 Document Name SEH50 SEH100 SEH200_OM Page 11 of 12 www ionproducts net Notes...

Страница 12: ...orrect a defect in a product shall extend the Warranty beyond the period set forth above Metropolitan shall not be obligated to remedy any defect where otherwise required pursuant to the Warranty unle...

Отзывы: