Communication extension card
EtherNet/IP communication card
-64-
Function
code
Word
Value range
Default
value
(0–1000, in which 1000 corresponds to 100.0% of the
rated voltage of the motor)
12: AO output setting 1 (-1000–+1000, in which 1000
corresponds to 100.0%)
13: AO output setting 2 (-1000–+1000, in which 1000
corresponds to 100.0%)
14: MSB of position reference (signed number)
15: LSB of position reference (unsigned number)
16: MSB of position feedback (signed number)
17: LSB of position feedback (unsigned number)
18: Position feedback setting flag (position feedback can
be set only after this flag is set to 1 and then to 0)
Response packet (VFD -> master station)
SW: The first word in a PZD response packet is a VFD SW. When P16.56=0, EtherNetIP
control words are defined by byte. Table 5-8 describes Goodrive350 series VFD SWs defined
by byte.
Table 5-8 Goodrive350 series VFD SWs defined by byte
Bit
Name
Value
Description
0–7
Running state
1
In forward running
2
In reverse running
3
Stopped
4
Faulty
5
POFF
8
Bus voltage establishment
1
Ready to run
0
Not ready to run
9–10
Motor group feedback
0
Motor 1
1
Motor 2
11
Motor type feedback
1
Synchronous motor
0
Asynchronous motor
12
Overload alarm feedback
1
Overload alarm generated
0
No overload alarm generated
13–14
RUN/STOP MODE
(Run/Stop mode)
0
Keypad-based control
1
Terminal-based control
2
Communication-based control
3
Reserved
15
HEARTBEAT FEEDBACK
(Heartbeat feedback)
1
Heartbeat feedback
0
No heartbeat feedback