Goodrive350-19 series VFD for crane
Commissioning guidelines
-56-
5.5.4 Points for attention
1. If you only want to check whether the VFD runs properly, set P90.00=0(Common mode).
2. If you perform empty-load commissioning, set P90.00=15 to select the application macro for
tower crane slewing without vortex in space voltage vector control.
3. During onsite commissioning, if the VFD terminal signal forward/reverse running command is
inconsistent with the load running direction, adjust any two phase sequences of VFD output
terminals U, V, and W.
4. This macro can meet the requirements of most application cases for tower crane rotating (without
vortex) in space voltage vector control, and the performance parameters have been optimized
and do not need to be adjusted in most cases. If an exception occurs, see the function parameter
chapter for adjustment or contact the technical support.
5.6 Conical motor function
5.6.1 Wiring
(+)
PB
VFD
R
S
T
R
S
T
M
3~
U
V
W
PE
S1
S2
S3
S4
HDIA
VFD fault output
RO1A
RO1B
RO1C
FWD run
REV run
Multi-step speed giving terminal 1
Coasting to stop
Fault reset
Braking resistor
COM
PW
+24V
Figure 5-8 Wiring for the conical motor
Note: If the wiring is performed according to Figure 5-8, most VFD parameters need no adjustment. If
the onsite function terminals are inconsistent with the terminals shown in the figure, adjust the input
and output terminal functions according to the actual wiring after selecting this application macro.
5.6.2 Commissioning procedure
1. Check the wiring and ensure the wiring is proper.
2. Set P00.18=1 to restore to default settings.
3. Set motor parameters in P02.
4. Set P90.00=5 to select the conical motor application macro.