Goodrive350-19 series VFD for crane
Function parameter list
-354-
Function
code
Name
Description
Default
Modify
, and the last time is equal to or greater
than
, the VFD reports a low-speed
running protection fault (LSP).
setting range: 0.000
–50.000s
setting range: 0.00
–20.00Hz
P92.04
Overload
protection current
detection value
When P92.38=1 overload protection is enabled.
When
>0, if the ramp frequency is equal
to or greater than (
+2.00Hz) during
upward running, the VFD starts checking the
current (closed-loop torque current or
open-closed output current). If the current is
equal to or greater than
, the VFD reports
the overload protection alarm after the detection
time reaches
. This restriction is not
applicable to downward running.
P92.04
P90.16
P90.16+2Hz
P92.05
Torque
current
%
Output
frequency
Relay
output
Normal
A-OL
setting range: 0.0
–150.0% (relative to the
motor rated torque in closed-loop state; relative
to the motor rated current in open-loop state; 0
indicates disabling)
setting range: 0.0
–5.0s
0.0%
◎
P92.05
Overload
detection time
0.5s
○
P92.06
Brake detection
reminding interval
When
>0, the brake detection reminding
function is enabled, if the accumulative running
time of the VFD is equal to or greater than
, the signal indicator is controlled through
0.0
◎
P92.07
Brake detection
reminding hold
5
○