Goodrive350 IP55 High-ingress Protection Series VFD
Function parameter list
-137-
Function
code
Name
Description
Default
value
Modify
6: Multi-step torque
7: Modbus/Modbus TCP communication
8: PROFIBUS/CANopen/DeviceNet
communication
9: Ethernet communication
10: Pulse frequency HDIB
11: EtherCAT/PROFITNET/Ethernet IP
communication
12: PLC
Note: For these settings, 100% corresponds
to the motor rated current.
P03.12
Torque set by
keypad
-300.0%
–300.0% (rated motor current)
20.0%
○
P03.13
Torque
reference filter
time
0.000
–10.000s
0.010s
○
P03.14
Source of upper
limit frequency
setup of forward
rotation in torque
control
0: Keypad (
1: AI1
2: AI2
3: AI3
4: Pulse frequency HDIA
5: Multi-step
6: Modbus/Modbus TCP communication
7: PROFIBUS/CANopen/DeviceNet
communication
8: Ethernet communication
9: Pulse frequency HDIB
10: EtherCAT/PROFITNET/Ethernet IP
communication
11: PLC
12: Reserved
Note:
For these settings, 100% corresponds to
the max. frequency.
0
○
P03.15
Source of upper
limit frequency
setup of reverse
rotation in torque
control
0: Keypad (P03.17)
1
–11: the same as P03.14
0
○
P03.16
Keypad limit
value of upper
forward rotation
in torque control
This function code is used to set frequency limit.
100% corresponds to the max. frequency.
sets the value when
=1.
Setting range: 0.00Hz
frequency)
50.00Hz
○
P03.17
Max. output
frequency
50.00Hz
○
P03.18
Source of upper
limit setup of the
0: Keypad (P03.20)
1: AI1
0
○