GD310-UL series VFD
Basic operation instruction
-134-
Function
code
Name
Description
Default value
P12.22
Quadrature axis inductance
of SM 2
0.01
–655.35mH
Depend on model
P12.23
Back EMF constant of SM 2 0
–10000
300
7.7 Start-up and stop control
The start-up and stop control of the VFD includes three states: start after the running command during
normal powering on, start after the restarting function becomes valid during normal powering on and
start after the automatic fault reset. Below is the detailed instruction for three startings.
There are three starting methods for the VFD: start from the starting frequency directly, start after the
AC braking and start after the rotation speed tracking. The user can select according to different
situations to meet their needs.
For the load with big inertia, especially in the cases where the reverse rotation may occur, it is better
to select starting after DC braking and then starting after rotation speed tracking.
Note
: it is recommended to use the direct starting to drive synchronous motor.
1. The starting logic figure of starting after the running command during the normal powering on
Jogging running?
N
1
f
1
t
P00.11
ACC time
P00.12
DEC time
A
C
C
D
E
C
P00.03
A
C
C
D
E
C
P00.03
1
f
1
t
P08.07
ACC time
P08.08
DEC time
A
C
C
D
E
C
P08.06
1
t
1
f
1
t
Jumping
frequency 2
1/2*jumping range 2
1/2*jumping range 2
Jumping
frequency1
1/2*jumping range 1
1/2*jumping range 1
Jumping
frequency3
1/2*jumping range 3
1/2*jumping range 3
Y
Start after rotation speed tracking
P01.00
Starting running
Start directly
The starting
frequency
The starting frequency
The retention time
The braking time before
starting
The braking
current
before
starting
P01.05
ACC/DEC method selection
P00.11
ACC time
P00.12
DEC time
0
1
2
0
1
Linear ACC/DEC
S curve ACC/DEC
Start directly
Start after DC braking
Jogging running
frequency
1
f