Goodrive300-21 integrated machine for air compressor
Commissioning guidelines
-
19
-
Function code Configuration value
Description
P00.00
0 or 2
0: Vector control (SM)
2: VF control (AM)
Select according to the motor type.
P00.01
2
2: Communication
P00.06
7
Main frequency PID control setting
P01.15
35.00
Stop frequency: 35Hz
P03.27
1
Vector control speed displayed by set value
P09.00
10
Pressure setting for air compressor
P09.02
8
Pressure feedback for air compressor
P11.15
0
No speed deviation protection
P05.01
6
Coast to stop
P05.10
3
Reverse S1, S2 terminal polarities
P05.02
46
External fault (motor over-temperature)
P06.03
28
Solenoid valve control output
P06.04
29
Fan start/stop control
P05.32
2.04
P1 lower limit corresponds to voltage 2.04V
Step 4 In system configuration interface,
click “System parameters setting”. When S1 functions as
emergency-stop switch, select
NO
or
NC
based on the polarity of the emergency-stop switch. When
S2 functions as motor overtemperature switch, select
NC
based on the polarity.
Figure 4-13 System parameter configuration interface
Set pressure sensor parameter, temperature sensor parameter and specialized function parameter
according to system sensor configuration condition. Then, click “Return” to enter system configuration
page.