Invicta pharos Скачать руководство пользователя страница 4

   PAGE 4

OBLICA

 | PHAROS INSTALLATION AND USER MANUAL

MINIMUM CLEARANCE – INTERNAL

2.1 Clearance from non-combustible surfaces 
(eg masonry)

100mm minimum clearance is required from fully 
non-combustible surfaces.

10
0

100

Non Combustible

Non Combus

tibl
e

2.2  Clearance from glass

400mm minimum clearance is required from normal 
non-combustible glass.

2.3  Clearance from combustible surfaces 
(eg timber joist & concrete) 

Clearances may be reduced with the application of 
heat shielding to walls in accordance to the 
Australian Building Code. 

For information on heat shielding please contact our 
office on 03 9416 0400 or email [email protected].

IMPORTANT: 

Frames must also be considered. Timber window 
frames must be treated as combustible surfaces 
(see 2.3). Aluminium frames can be treated as 
non-combustible surfaces (see 2.2).  

2. PRE-INSTALLATION 

(CONTINUED)

Glass (frameless or aluminium frame)

Glas

s (fr

amel

es
s or aluminium fr

ame)

400mm

400mm

625mm

Combustible

Combus

tibl
e

625mm

Combustible

Combus

tibl
e

750mm

750mm

Configuration 1 – Parallel installation

Configuration 2 – Corner installation

Содержание pharos

Страница 1: ...PHAROS MODEL SPECIFICATIONS 1 TECHNICAL DATA 2 2 PRE INSTALLATION 3 3 INSTALLATION 5 4 OPERATION 9 5 TESTING 10 Keep for future use...

Страница 2: ...AL DATA WEIGHT AND DIMENSIONS Dimensions Firebox W531 x H1250 x D530mm Firebox weight 167kg Flue kit Standard 7 9 11 DETERMINED UNDER TEST CONDITIONS Nominal thermal output 9kW Efficiency Australian T...

Страница 3: ...l flue and engage the firebox Ensure the floor has adequate protection CAUTION Using components or parts other than those provided by the manufacturer or modifying the specification of components may...

Страница 4: ...ith the application of heat shielding to walls in accordance to the Australian Building Code For information on heat shielding please contact our office on 03 9416 0400 or email info oblica com au IMP...

Страница 5: ...HAROS INSTALLATION AND USER MANUAL 3 INSTALLATION 3 1 Typical flue kit installation Cowl Chinaman Hat 9 Outer Case 11 Outer Case 9 Outer Case 11 Outer Case 7 Active Flue 7 9 Flue CEILING RING RUBBER D...

Страница 6: ...he triple skin flue is installed as per Australian standards see diagrams below The top of the flue must be 400mm higher than the highest point of the roof Alternatively there must be a minimum distan...

Страница 7: ...combustiblefinishescanbeappliedtothefloorprotector tiles steelsheet lightconcrete etc If the combustible floor is installed on concrete you can replace the combustible material with non combustible ma...

Страница 8: ...TALLATION AND USER MANUAL Non combustible finish eg tiles Concrete Combustible floor eg timber 300mm 730mm 810mm Combustible floor eg Timber Floor protector FLOOR PROTECTOR LAID ON CONCRETE 3 INSTALLA...

Страница 9: ...s to start or rekindle the fire Do not use flammable liquids or aerosols in the vicinity of the fireplace when operating Do not store fuel within prescribed installation clearance distances The use of...

Страница 10: ...5 INVESTIGATING OFFICER Steve Marland RESULTS The Pharos solid fuel burning appliance produced an appliance particulate emissions factor of 1 2g kg and an average efficiency of 60 for all burn rates u...

Отзывы: